ZP3 Fire Control Panel Installation, Commissioning and Maintenance Manual
REV 11 (ISS 08/03/2010)
Page 119
Checksums
Two numeric values are printed, a calculated value and a stored value. If the two values
are not equal, then code corruption has occurred.
Stop printer
This option is used to cancel any print operation in progress.
Calibrate detectors
Menu path
Maintenance/Calibrate detectors
Purpose
The panel automatically calibrates every sensor each 24 hours, at midnight.
This menu allows you to manually re-calibrate the sensors. When initiated a message
"Calibrating…" is displayed on the LCD screen while calibration takes place. This takes
about one minute to complete.
Test
Menu path
Maintenance/test
Purpose
This menu allows you to configure automatic and manual test modes to provide simple
one-man testing of a complete system.
Detector test
Sensors can be individually or globally configured to "self-test" every 24 hours. This test is
done at midnight, and a report is generated if any sensors fail the test.
The self test routine can be manually initiated from within this menu for an immediate
real time test. The display indicates the number of detectors tested and passed. A fault
event is generated if failure occurs. If a printer is fitted, a report is automatically printed.
Walk test
The walk test procedure is executed on a zonal basis. A zone is placed in "walk-test"
mode, and the sensors/devices within the zone are manually tested. The outputs and
alarms for the selected zone are automatically disabled. At the end of the test, the display
shows the number of devices in the zone, the number triggered and passed, and the
number not triggered and failed. The respective zone LED on the fire panel is lit. A printed
report is also produced. If an alarm occurs in a different zone, the panel cancels the test,
and initiates a real alarm.
Flash faulty LED
Enabling this function flashes the LED on a point that reports a fault. This assists with
visually finding and identification of the device that reports a fault.
Comms enable/disable
Menu path
Maintenance/Comms enable/disable
Purpose
This menu allows you to enable or disable PP3 comms to panels on the Network
temporarily, without altering their filters etc. When edited on one panel it replicates to all
panels that are configured to be online via setup, so that they all agree on who is
expected to be online.
Operation
When Comms enable/disable is selected, the following menu is displayed (see Figure 72). The
panel number, which defaults to 001, can be entered using the panel keypad.
Figure 72: Maintenance: Comms Enable/disable
As the panel number is entered, the panel status will change accordingly. The panel status can
either be Enabled, Disabled, Offline or Invalid. An invalid panel number results in an invalid
condition, which is indicated by a blank in the panel status field.
Содержание ZP3
Страница 1: ...GE Security ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual ...
Страница 44: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 32 REV 11 ISS 08 03 2010 ...
Страница 56: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 44 REV 11 ISS 08 03 2010 ...
Страница 142: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 130 REV 11 ISS 08 03 2010 ...
Страница 143: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual REV 11 ISS 08 03 2010 Page 131 ...
Страница 144: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 132 REV 11 ISS 08 03 2010 ...