ZP3 Fire Control Panel Installation, Commissioning and Maintenance Manual
Page 4
REV 11 (ISS 08/03/2010)
Description Specification/
parameters
Remarks
Power supply (external)
Primary supply
24 to 28 VDC,
(Amps dependant
on system load)
Optional - Supplied from an external charger
Output (mains OFF)
24 VDC
15 to 27.6 VDC depending upon state of battery and
load
Total output
Amps
Dependent on external charger capacity
User available output
Amps
Dependent on external charger
Secondary supply/battery
24 VDC
Capacity dependent upon external charger
Software
Part number
71900
Version 2.0 or higher
Firmware -
Flash
memory
Configuration programming
-
Flash memory
Display
Liquid crystal text display
160 characters
Backlit 4 line text display
LED indicators
87
High-efficiency LED’s for status indication
Communication ports
Z-Port 1
Planner (RS232)
Built-in RS232 for loading configuration from Planner
(without control lines)
Z-Port 2
ZP-Net (RS485)
Optional RS485 port for connecting to ZP-NET
Serial control bus
SCB-Bus (RS485)
Optional port for remote display and control panels
Z-Port 1a
RS232
Optional port for BMS, Pager, or other connection
(with Modem control lines)
Selectable features
Common sounders
EN54-2
Four common sounder circuits
Co-incidence alarm
EN54-2
Co-incidence within zone
Remote manned centre (fire)
EN54-2
For connection to fire alarm RMC routing equipment
Remote manned centre (Fault)
EN54-2
For connection to fault alarm RMC routing equipment
Zone walk test
EN54-2
One-man test of a zone, other zones remain working
Control outputs
EN54-2
Up to 768 programmable control outputs
Output delays
EN54-2
Delays can be programmed to any output
Alarm counter
EN54-2
Level 2 access alarm counter records all alarms
Delay on sounder silence
Prevents silencing alarms before they are heard
Alarm verification
Verifies alarms from a sensor before displaying “Fire”
Sensor sensitivity
Four levels of sensitivity per sensor
Input - output configuration
Sophisticated I/O mapping functions
Automatic sensor test
Tests complete operation of sensors
Содержание ZP3
Страница 1: ...GE Security ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual ...
Страница 44: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 32 REV 11 ISS 08 03 2010 ...
Страница 56: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 44 REV 11 ISS 08 03 2010 ...
Страница 142: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 130 REV 11 ISS 08 03 2010 ...
Страница 143: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual REV 11 ISS 08 03 2010 Page 131 ...
Страница 144: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 132 REV 11 ISS 08 03 2010 ...