ZP3 Fire Control Panel Installation, Commissioning and Maintenance Manual
REV 11 (ISS 08/03/2010)
Page 77
Planner
Most of the programming of a ZP3 system is done by means of software. This can be done
directly via the panel menus, or it can be done off-line on a PC, using Ziton Planner software, and
later loaded into the panel by means of a serial data connection. After being loaded into the
panel, minor modifications can be done to the programming, directly via the panel menus. In this
case, it is possible to load the programming from the panel back to the PC, for saving to disk, and
hard-copy printout and record keeping.
The menu path is: Setup/Planner. Menu options available are as follows (see Table 24).
Table 24: Planner setup options
Option Description
Send map
This function is used to send the programmed data that exists in a ZP3 panel to an
external PC.
Receive map
This function is used to receive programmed data from a PC.
Note:
The preferred baud rate settings when using Planner to configure a ZP3 panel are:
Baud
rate Bits
Odd/even
Receive
38400
8 Even
1
Send
9600
8 Even
1
Alternatively you can set Z-Port 1 to ‘ZCP3’ to allow control directly from Planner.
Level 4 operations
These are high level operations for use by a senior administrator of the fire system, to carry out
settings which cannot be changed by installation, maintenance, or operation personnel.
The menu path is: Setup/Level 4 operations. The following options are available (see Table 25).
Table 25: Level 4 operation setup options
Option Description
Security codes
Allows you to define panel access codes as follows:
1. Operator
2. Maintenance
3. Setup
4. Level 4
In addition, the access system allows you to enter up to 20 (optional) operator names.
Each name can have a different 4-digit numeric access code, and have an access level of
1-4.
Clear - This menu allows you to delete all the access codes. The existing level4 code is
required for deletion and a new level4 code is required.
Edit/View - This menu allows for viewing, adding new codes, and deleting codes. The first
operator, code and access level is displayed. Scroll to display other entries. Displayed
entries can be deleted. To add an entry, scroll to the end of the list and enter the required
details.
Print: - This option generates a printed record of all existing Operator names, codes and
levels, to provide a hard copy record.
Local Program'ng
A setting to allow programming to be done by two options, as follows:
Local programming enabled - Panel can be programmed directly from the keypad (level3
access), or externally by PC and loaded into the panel.
Local programming disabled Panel cannot be programmed via the keypad, it can only
be programmed externally by PC and loaded into the panel.
Erase program
Selecting this option deletes all user programming and restores all configuration settings
to the factory defaults.
Содержание ZP3
Страница 1: ...GE Security ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual ...
Страница 44: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 32 REV 11 ISS 08 03 2010 ...
Страница 56: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 44 REV 11 ISS 08 03 2010 ...
Страница 142: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 130 REV 11 ISS 08 03 2010 ...
Страница 143: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual REV 11 ISS 08 03 2010 Page 131 ...
Страница 144: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 132 REV 11 ISS 08 03 2010 ...