Points: individual setting: view
This menu enables the operator to view the configurations of individual points connected to the
Z-loops.
The menu path is: Setup/Points/Individual Settings/View. The available options are provided in
Table 12.
Table 12: Individual point settings view options
Option Description
Sensitivity/AVF
View the sensitivity to which a sensor is set. The following options are available after
accessing this menu:
Sensitivity point: - Sensitivity settings for an individual point. Enter the point address. The
device type, zone and sensitivity settings are displayed. Use the scroll feature to view the
next/previous point.
Sensitivity point range - Sensitivity settings viewed on a group basis by zone and device
type. Enter the zone range (or all), and the device types (or all) and then use the scroll
feature to view.
AVF point: - Alarm verification settings for an individual point. Enter the point address. The
device type, zone and AVF setting are displayed. Use the scroll feature to view the
next/previous point.
AVF point range - Alarm verification settings viewed on a group basis by zone and device
type. Enter the zone range (or all) and device type (or all) and then use the scroll feature to
view.
Zones
View the point addresses of all devices allocated to a zone. Enter the zone number to be
viewed. The zone number and first point address in that zone is displayed. Use the scroll
feature to view the next/previous address in that zone.
Messages
View the identification message assigned to each point address. Enter the point address.
The message is displayed. Use the scroll feature to view the previous/next point address.
Sounder
View which sensors are fitted with sounder bases. The address of the first sensor with
sounder base is displayed together with the total number of sensor/sounder base points.
Use the scroll feature to view the list.
Detector test
View which sensors have their self-test feature enabled. Enter the point address for the
point to be viewed. Use the scroll feature to view the previous/next point.
Point type
View which the type of device at each address. Enter the point address. The device type is
displayed. Use the scroll feature to view the previous/next address.
AGV allocation
View which sensors are allocated into each "Alarm Group". See the "Edit" section for more
details on AGV.
Содержание ZP3
Страница 1: ...GE Security ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual ...
Страница 44: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 32 REV 11 ISS 08 03 2010 ...
Страница 56: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 44 REV 11 ISS 08 03 2010 ...
Страница 142: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 130 REV 11 ISS 08 03 2010 ...
Страница 143: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual REV 11 ISS 08 03 2010 Page 131 ...
Страница 144: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 132 REV 11 ISS 08 03 2010 ...