ZP3 Fire Control Panel Installation, Commissioning and Maintenance Manual
REV 11 (ISS 08/03/2010)
Page 23
Setup
The ZP3 panel can operate 63 remote display units. The address range for the RDU is 1 to 63,
which allows for up to 63 address options. The RDU is wired to the panel via the ZP3AB-SCB1 SCB
driver board.
Usage
: Fit the ZP3AB-SCB1 board to the ZP3 panel using the interface marked 'RDU interface'.
Accept devices on the panel. The SCB software stream for the 71910 EN panel is SW72401. Once
the SCB driver board has been accepted the user can view the SCB driver software under
operator/reports to display. Configure the SCB online, this defines the number of RDUs that can
be connected to the panel.
Navigate to the following menu:
Setup/System configuration/peripheral comms/RDU/SCB on line
The address of an RDU may not be higher than the number of RDUs configured to be to online. If
this value is set to 32 then RDUs can be connected with addresses ranging from one to 32. This
number defines the valid RDU address numbers and not the amount of RDUs connected. All RDUs
that have addresses higher than the number entered for RDUs online will not have control
abilities.
If this number is set to 63, the address at the RDU can be set to any address from 1-63. If this
number is set to 1, only address 1 can be set on the RDU unit.
Remote display unit
When a RDU is configured as being online, it mimics the panel and also sends control information
back to the panel. To disable the RDU control, remove the controls enabled jumper fitted to the
RDU board. The RDU software stream for the 71910 EN panel is SW72201. Once the RDU has
been accepted the user can view the RDU software under operator/reports to display. If there are
ten RDUs accepted then this menu will have ten entries for RDUs.
Usage
: The number selected on the address switch depends on the number of RDUs defined
online. As stated above, the number entered to define the amount of RDUs online defines the
maximum address number. Address switches 1, 2, 3, 4, 5 and 6 set the address in the standard
address switch format as used on the detectors, e.g. switches 2, 3, 4, 5 and 6 set to ON represent
an RDU address of 62.
Содержание ZP3
Страница 1: ...GE Security ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual ...
Страница 44: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 32 REV 11 ISS 08 03 2010 ...
Страница 56: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 44 REV 11 ISS 08 03 2010 ...
Страница 142: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 130 REV 11 ISS 08 03 2010 ...
Страница 143: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual REV 11 ISS 08 03 2010 Page 131 ...
Страница 144: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 132 REV 11 ISS 08 03 2010 ...