ZP3 Fire Control Panel Installation, Commissioning and Maintenance Manual
REV 11 (ISS 08/03/2010)
Page 75
System configuration: relays
This menu is used to set the common functions of the panel. The Relays menu allows for the
setup of the standard built-in relays.
The menu path is: Setup/System Configuration/Relays. The following options are available (see
Table 21).
Table 21: System configuration relay setup options
Option Description
Fire Relay
The common fire relay can be set to normally de-energised (open contact, closing on
alarm) or normally energised (closed contact, open on alarm). The latter state is described
as "inverted" in the menu.
Fault Relay
The common fault relay can be set to normally energised (open contact, closing on alarm)
or normally de-energised (closed contact, open on alarm). The latter state is described as
"inverted" in the menu.
RMC Alarm
The remote manned centre output is connected to RMC-routing equipment. It should be
set to restore only after a reset.
Sounder Relays
The sounder outputs (4 outputs, controlled from 2 addresses) can be set to operate as
"common", from any alarm, or as programmable. If set to programmable, then they must
be linked to activating inputs in the I/O-menu.
System configuration: printer
This menu is used to set the common functions of the panel. The Printer menu allows for the
setup of the optional in-panel printer.
The menu path is: Setup/System Configuration/Printer. The following options are available (see
Table 22).
Table 22: System configuration printer setup options
Option Description
Printer type
Allows the type of printer to be defined. Current types are:
1. NONE
no printer attached
2. Able-24/25
panel printer
(3. Able-24+IN)
panel printer
4. Serial desktop external printer 80 column
Printer options
Defines the information to be printed,. categories are:
1. Fire Alarm
2. Fault
3. Panel Operation
4. O/P Activation
Содержание ZP3
Страница 1: ...GE Security ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual ...
Страница 44: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 32 REV 11 ISS 08 03 2010 ...
Страница 56: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 44 REV 11 ISS 08 03 2010 ...
Страница 142: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 130 REV 11 ISS 08 03 2010 ...
Страница 143: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual REV 11 ISS 08 03 2010 Page 131 ...
Страница 144: ...ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual Page 132 REV 11 ISS 08 03 2010 ...