![GE Multilin F650 Скачать руководство пользователя страница 607](http://html.mh-extra.com/html/ge-multilin/f650/f650_instruction-manual_572016607.webp)
CHAPTER 7: IEC 61850 PROTOCOL
7.2 IEC 61850 PROFILE FOR F650
GEK-106310-AF
F650 DIGITAL BAY CONTROLLER
7-201
7.2.7.3.12 PIXIT for 650 family of relays whose order code has Rear Ethernet Communication Board 2
option "H", "G", "K", "J", "L", "M" and IEC 61850 Edition 1
Reference documentation:
PIXIT For F650 relay V1_10 firm7_52
.
This document specifies the protocol implementation extra information for testing (PIXIT) of the IEC 61850 interface in:
F650 Bay Controller with firmware version 7.52
Together with the PICS and the MICS the PIXIT forms the basis for a conformance test according to IEC 61850-10. The PIXIT
entries contain information which is not available in the PICS, MICS, TICS documents or SCL file.
Each table specifies the PIXIT for applicable ACSI service model as structured in IEC 61850-10. The "Ed" column indicates if
the entry is applicable for IEC 61850 Edition 1 and/or Edition 2.
1 Pixit For Association Model
ID
Ed
Description
Value / Clarification
As1
1
Maximum number of clients that can set-up an association
simultaneously
5
As2
1, 2
TCP_KEEPALIVE value. The recommended range is 1..20s
5 seconds but if no application message is
detected within the As3 value, the device
closes the connection.
As3
1, 2
Lost connection detection time
120 seconds (Configurable)
As4
-
Authentication is not supported yet
As5
1, 2
What association parameters are necessary for successful
association
Transport selector
Y
Session selector
Y
Presentation selector
Y
AP Title
N
AE Qualifier
N
As6
1, 2
If association parameters are necessary for association, describe
the correct values e.g.
Transport selector 0001
Session selector
0001
Presentation selector 00000001
AP Title
NA
AE Qualifier
NA
As7
1, 2
What is the maximum and minimum MMS PDU size
Max MMS PDU size 120000
Min MMS PDU size
7000.
As8
1, 2
What is the maximum start up time after a power supply interrupt
90 seconds
Содержание F650
Страница 68: ...2 32 F650 DIGITAL BAY CONTROLLER GEK 106310 AF 2 6 EXTERNAL CONNECTIONS CHAPTER 2 PRODUCT DESCRIPTION ...
Страница 406: ...6 58 F650 DIGITAL BAY CONTROLLER GEK 106310 AF 6 5 RECORDS CHAPTER 6 ACTUAL VALUES ...
Страница 660: ...7 254 F650 DIGITAL BAY CONTROLLER GEK 106310 AF 7 3 IEC 61850 CONFIGURATOR CHAPTER 7 IEC 61850 PROTOCOL ...
Страница 734: ...12 6 F650 DIGITAL BAY CONTROLLER GEK 106310 AF 12 4 RELAY CONFIGURATION CHAPTER 12 FREQUENTLY ASKED QUESTIONS ...
Страница 772: ...A 32 F650 DIGITAL BAY CONTROLLER GEK 106310 AF A 1 OPERANDS F650 MODEL FX GX APPENDIX A LOGIC OPERANDS ...
Страница 950: ...c 24 F650 DIGITAL BAY CONTROLLER GEK 106310 AF C 8 ANALOG INPUTS APPENDIX C DNP 3 0 PROTOCOL FOR F650 ...
Страница 994: ...H 2 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Страница 995: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 3 ...
Страница 996: ...H 4 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Страница 998: ...H 6 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Страница 999: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 7 ...
Страница 1002: ...H 10 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Страница 1003: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 11 ...
Страница 1004: ...H 12 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Страница 1044: ...I 40 F650 DIGITAL BAY CONTROLLER GEK 106310 AF I 2 FACTORY DEFAULT CONFIGURATION APPENDIX I FACTORY DEFAULT CONFIGURATION ...
Страница 1046: ...J 2 F650 DIGITAL BAY CONTROLLER GEK 106310 AF J 1 GE MULTILIN WARRANTY APPENDIX J MISCELLANEOUS ...