GASSONIC OBSERVER-i
40
4.5.11. Setting HART Analog Output Range (only if HART is on)
The Gassonic Observer-i provides the operator the ability to field configure the unit to either 3.5 mA or
1.25 mA minimum HART analog output.
Activate the MENU switch ten times with the magnet stick. The factory default setting (Ao35) will be
displayed. Activating the UP switch (
▲
) and DOWN switch (
▼
) will switch to select the minimum
current. Activating the ENTER switch having changed the status 35/12, will flash “SAVE” on the
display. Confirm the SAVE action by activating the ENTER switch once more. Activating the MENU
switch while “SAVE” is flashing, will discard the SAVE and switch the unit back to normal operation. If
ENTER is activated the unit will display “DONE” to confirm that the changes have been saved and
return to normal operation. The operator can change the HART setting and if desired move to the next
item (Baud Rate) in the menu structure by activating the MENU switch straight after the change. The
change will be saved at a later stage by activating the ENTER switch at any point in the menu
structure. If no switch is activated for 60 seconds, the detector will return to normal operation without
saving the changed settings.