GASSONIC OBSERVER-i
38
4.5.9. Switching
HazardWatch Mode ON/OFF
Activate the MENU switch eight times with magnet stick. The factory default setting (HZOF) will be
displayed. Activating the DOWN switch (
▼
) will switch the factory default ON (FD ON). Activating the
UP switch (
▲
) will switch the factory default OFF. Activating the ENTER switch having changed the
status ON/OFF, will flash “SAVE” on the display. Confirm the SAVE action by activating the ENTER
switch once more. Activating the MENU switch while “SAVE” is flashing, will discard the SAVE and
switch the unit back to normal operation. If ENTER is activated the unit will display “DONE” to confirm
that the changes have been saved and return to normal operation. The operator can change the
HazardWatch settings and if desired move to the next item (HART ON/OFF) in the menu structure by
activating the MENU switch straight after the change. The change will be saved at a later stage by
activating the ENTER switch at any point in the menu structure. If no switch is activated for 60
seconds, the detector will return to normal operation without saving the changed settings.