GASSONIC OBSERVER-i
32
4.5.4. Setting / Checking Cut-Off Frequency (Enhanced Mode only)
In Enhanced Mode the cut-off frequency of the unit can be set between high (FQHI) and low (FQLO). The
factory default setting is “FQHI” to eliminate spurious alarms in ultra-high noise areas. This setting can be
set to “FQLO” in medium and low noise areas, which will still allow ANN to protect against spurious alarms
and have a slight increase in coverage.
Activate the MENU switch three times with the magnet-stick. The current cut-off frequency will be displayed
(factory setting FQHI). Activating the UP switch (
▲
) or DOWN switch (
▼
) will toggle between “FQHI” and
“FQLO”. Activating the ENTER switch without changes made, switches the unit back to Normal Operation.
Activating the ENTER switch with changes made, will flash “SAVE” on the display. Confirm the save action
by activating the ENTER switch once more. Activating the MENU switch while “SAVE” is flashing, will
discard the save and switch the unit back to Normal Operation. If ENTER was activated the unit will display
“DONE” to confirm that the changes have been saved and return to Normal Operation.
The operator can change the cut-off frequency and if desired move to the next item (delay time) in the
menu structure by activating the MENU switch straight after the change. The change will be saved at a
later stage by activating the ENTER switch at any point in the menu structure. If no switch is activated for
60 seconds the detector will return to normal operation without saving the changed settings.
Содержание Observer-i
Страница 2: ...GASSONIC OBSERVER i ii This page intentionally left blank ...
Страница 16: ...GASSONIC OBSERVER i 16 Figure 7 Internal Earth Terminal ...
Страница 24: ...24 4 G GASSONIC C OBSERV VER i ...
Страница 37: ...GASSONIC OBSERVER i 37 ...
Страница 51: ...GASSONIC OBSERVER i 51 Figure 9 Calibration Routine ...