GASSONIC OBSERVER-i
53
6.3.2. Modbus Read Response Message
Byte
Modbus
Range
Referenced to Gassonic
Observer-i
1
st
Slave
Address
1-247
*
(Decimal)
Gassonic Observer-i ID (Address)
2
nd
Function
Code
03 or 04
Read Holding Registers
3
rd
Byte Count
02 – FF (Hex)
No. of Data Bytes
4
th
Data Hi
00-FF (Hex)
Gassonic Observer-i Hi Byte
Status Data
5
th
Data Lo
00-FF (Hex)
Gassonic Observer-i Lo Byte
Status Data
6
th
CRC Lo
00-FF (Hex)
CRC Lo Byte
7
th
CRC Hi
00-FF (Hex)
CRC Hi Byte
Table 7: Modbus Read Response Messages
NOTE:
Address 0 is reserved for broadcast mode and will not be supported at this time.
6.4. Modbus
Write
Command
Protocol (Query/Response)
6.4.1. Modbus Write Query Message
Byte
Modbus
Range
Referenced to Gassonic
Observer-i
1
st
Slave
Address
1-247
*
(Decimal)
Gassonic Observer-i ID (Address)
2
nd
Function Code
06
Preset Single Register
3
rd
Register
Address
Hi
**
00
Not used by Gassonic Observer-i
4
th
Register Address
Lo
**
00-FF (Hex)
Gassonic Observer-i Commands
5
th
Preset Data Hi
00-FF (Hex)
Gassonic Observer-i Hi Byte
Command Data
6
th
Preset Data Lo
00-FF (Hex)
Gassonic Observer-i Lo Byte
Command Data
7
th
CRC Lo
00-FF (Hex)
CRC Lo Byte
8
th
CRC Hi
00-FF (Hex)
CRC Hi Byte
Table 8: Modbus Write Query Message
NOTE*:
Address 0 is reserved for broadcast mode and is not be supported at this time.
NOTE
**
:
Start Address can be a maximum of 247 Address Locations (0000-0x00F7).
Содержание Observer-i
Страница 2: ...GASSONIC OBSERVER i ii This page intentionally left blank ...
Страница 16: ...GASSONIC OBSERVER i 16 Figure 7 Internal Earth Terminal ...
Страница 24: ...24 4 G GASSONIC C OBSERV VER i ...
Страница 37: ...GASSONIC OBSERVER i 37 ...
Страница 51: ...GASSONIC OBSERVER i 51 Figure 9 Calibration Routine ...