4.5.6. Setting / Checking Alarm Relay Energized / De-Energized
The Alarm Relay is normally de-energized at power up of the unit. The output is an open contact. The
output can be changed to closed contact at alarm by energizing the Alarm Relay.
Activate the MENU switch five times with the magnet-stick. The current Alarm Relay status will be
displayed (factory setting = RLDE = de-energized). Activating the DOWN switch (
▼
) will switch the
Alarm Relay status to energized (RL E). Activating the UP switch (
▲
) will switch the Alarm Relay
status back to de-energized. Activating the ENTER switch without changes made, switches the unit
back to Normal Operation. Activating the ENTER switch with changes made, will flash “SAVE” on the
display. Confirm the save action by activating the ENTER switch once more. Activating the MENU
switch while “SAVE” is flashing will discard the save and switch the unit back to Normal Operation. If
ENTER was activated the unit will display “DONE” to confirm that the changes have been saved and
return to Normal Operation.
The operator can change the relay energizing settings and if desired move to the next item (alarm
latching ON/OFF) in the menu structure by activating the MENU switch straight after the change. The
change will be saved at a later stage by activating the ENTER switch at any point in the menu
structure. If no switch is activated for 60 seconds the detector will return to normal operation without
saving the changed settings.
Содержание Observer-i
Страница 2: ...GASSONIC OBSERVER i ii This page intentionally left blank ...
Страница 16: ...GASSONIC OBSERVER i 16 Figure 7 Internal Earth Terminal ...
Страница 24: ...24 4 G GASSONIC C OBSERV VER i ...
Страница 37: ...GASSONIC OBSERVER i 37 ...
Страница 51: ...GASSONIC OBSERVER i 51 Figure 9 Calibration Routine ...