4.5.8. Setting / Checking Factory Default ON / OFF
The Factory Default command gives the local operator the opportunity to return all settings to factory
default.
Activate the MENU switch seven times with the magnet-stick. Factory Default OFF (FDOF) will be
displayed. Activating the DOWN switch (
▼
) will switch the Factory Default ON. Activating the UP
switch (
▲
) will switch the Factory Default OFF. Activating the ENTER switch without changing the
status to ON, switches the unit back to Normal Operation. Activating the ENTER switch having
changed the status to ON, will flash “SAVE” on the display. Confirm the save action by activating the
ENTER switch once more. Activating the MENU switch while “SAVE” is flashing will discard the save
and switch the unit back to Normal Operation. If ENTER was activated the unit will display “DONE” to
confirm that all settings have been returned to the Factory Default and return to Normal Operation.
Activating the MENU switch a 12th time will switch the unit to Normal Operation, if any changes were
made in previous menu items (HazardWatch Mode ON/OFF) the unit will flash “SAVE” on the display.
Confirm the save by activating the ENTER switch or discard the save by activating the MENU switch
once more. If no switch is activated for 60 seconds the detector will return to normal operation without
saving the changed settings.
The Gassonic Observer-i factory default settings are as follows:
Feature
Setting
Modbus 1
Address 1, 8-N-1, 19200 baud
Modbus 2
Address 1, 8-N-1, 19200 baud
Trigger Level
54 dB
Trigger Delay
2 seconds
Alarm Relay – Energized / De-Energized
De-Energized
Alarm Relay – Latched / Un-Latched
Un-Latched
HART Enable
(Disabled)
HART Current
(Disabled)
Table 3: Dual Modbus Configuration Default Settings
Feature
Setting
Modbus 1
Address 1, 8-N-1, 19200 baud
Modbus 2
(Disabled)
Trigger Level
54 dB
Trigger Delay
2 seconds
Alarm Relay – Energized / De-Energized
De-Energized
Alarm Relay – Latched / Un-Latched
Un-Latched
HART Enable
Enabled
HART Current
3.5 mA for High Range;
1.25 mA for Low Range
Table 4: Single HART Configuration Default Settings
NOTE:
There are three other ways to restore the default values. Both Modbus and HART can
send a command. The alarm reset switch can restore the default values. (See remote reset
switch)
Содержание Observer-i
Страница 2: ...GASSONIC OBSERVER i ii This page intentionally left blank ...
Страница 16: ...GASSONIC OBSERVER i 16 Figure 7 Internal Earth Terminal ...
Страница 24: ...24 4 G GASSONIC C OBSERV VER i ...
Страница 37: ...GASSONIC OBSERVER i 37 ...
Страница 51: ...GASSONIC OBSERVER i 51 Figure 9 Calibration Routine ...