GASSONIC OBSERVER-i
26
Acoustic Error
The Gassonic Observer-i has failed the acoustic test.
Action
- Make sure the foam and all acoustic parts are clean. Replace the Sound
Source.
Remote Alarm Switch Stuck
The “remote alarm” is closed for 60 seconds.
Action
- Check the wiring on the remote alarm. Once the short circuit is cleared, the
unit will return to normal operation.
Remote Relay Reset Switch Stuck
The “remote reset” is closed for 30 seconds.
Action
- Check the wiring on the remote reset switch. Once the short circuit is cleared,
the unit will return to normal operation.
Magnetic Sensors Stuck
The “magnetic sensor stuck” is closed for 60 seconds.
One of the four magnet switches or a cable is shorted.
Action
- If the magnetic switch is shorted, the unit must be returned to the factory or
authorized service center for service.
Internal Voltage Error
The possible errors are an internal voltage is not at the proper value or a circuit is not
functioning properly.
Action
- An internal error has occurred. The unit must be returned to the factory for
service.
Critical Memory Error
This is a main memory error and the Gassonic Observer-i may not function correctly.
Action
– The unit must be returned to the factory or authorized service center for
repair.
User Memory Error
User memory includes the trigger level, delay time, latched/non-latched, energized/non-
energized, Modbus setting, or any other user changeable settings. This error indicates one or
more of these values are wrong.
Action
– Cycle power. The error will go away, but the data is still not correct. The
user must restore all user settings.
HART Memory Error
A HART memory register has an error. These registers contain HART user settings. This error
indicates one or more of these values are incorrect.
Содержание Observer-i
Страница 2: ...GASSONIC OBSERVER i ii This page intentionally left blank ...
Страница 16: ...GASSONIC OBSERVER i 16 Figure 7 Internal Earth Terminal ...
Страница 24: ...24 4 G GASSONIC C OBSERV VER i ...
Страница 37: ...GASSONIC OBSERVER i 37 ...
Страница 51: ...GASSONIC OBSERVER i 51 Figure 9 Calibration Routine ...