GASSONIC OBSERVER-i
14
3.3. Mounting
Two M8 stainless steel bolts (not supplied), 88 mm apart, attached to the top of the detector are used
to fix the Gassonic Observer-i in its operating position. These bolts may penetrate the detector top by a
maximum of 14 mm. The detector can be mounted to a freestanding pole or wall, using the Gassonic
mounting bracket 80601-1. This bracket is an optional accessory and is supplied with two M8 mounting
U-bolts which can fit around a pole with a maximum dimension of 63 mm. It is possible to mount the
detector directly onto non-vibrating structural beams or cable-trays. The microphone should face
downwards and if tilting of the detector is necessary, the angle of incline should not exceed 45°. When
mounting the detector within half a meter of a solid structure, such as a wall or a big vessel, the
acoustic test sound source shall be pointed away from the structure. The sound source should be
pointing into free space as far as possible.
Figure 4: Mounting Diagram