GASSONIC OBSERVER-i
30
4.5.2. Forced Acoustic Test
This will enable the local operator to test the acoustic properties of the unit. Activate the MENU switch
with the magnet-stick. The code “ATOF” (Acoustic Test Off) will be displayed. Activating the UP switch
(
▲
) will display the “wait” command followed by the sound level detected by the microphone emitted
from the sound source. If this value is flashing, the unit is failing the acoustic test. There could be a
number of causes for this error, see Section 8.3. for more information. The DOWN switch (
▼
) will stop
the acoustic test and display “ATOF”. Activating the ENTER switch at any time during this operation
will display “DONE” and take the unit back to Normal Operation. A maintenance event will be
recorded. If no switch is activated for 60 seconds the detector will return to normal operation.