GASSONIC OBSERVER-i
43
4.5.14. Modbus Setting: Address (Channel One)
Activating the MENU switch thirteen times will display the current Address of the Modbus (Factory
setting is 001). Activating the UP switch (
▲
) will increment the address and activating the DOWN
switch (
▼
) will decrement the address (the range is 1 to 247). Activating the ENTER switch having
changes made, will flash. “SAVE” on the display. Confirm the SAVE action by activating the ENTER
switch once more. Activating the MENU switch while “SAVE” is flashing, will discard the SAVE and
switch the unit back to normal operation. If ENTER is activated the unit will display “DONE” to confirm
that the changes have been saved and return to Normal operation. The operator can change the
address settings time and if desired move to the next item (Baud Rate) in the menu structure by
activating the MENU switch straight after the change. The change will be saved at a later stage by
activating the ENTER switch at any point in the menu structure. More info for Modbus protocol is
available in Section 6. If no switch is activated for 60 seconds the detector will return to normal
operation without saving the changed settings.