background image

 

Product Sheet 

GS7.05

 

 

 

Detector Type

 

RGI-CO0-L42

 

 
 
 

 
Online Store: 

www.syxthsense.com

 

Copyright 

©

 2005 SyxthSense Ltd – 01/2005 

Enquiries: T: 

0870 20 80 100

   F: 

0870 20 80 200

 PS 

GS7.05

– 1/1 

 

 

 

 

 

RGI-CO0-L42 Carbon Monoxide 
Gas Detection Unit 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Model Types 

Model Description 

 

RGI-CO0-L42 

Gas Leak Detector for Carbon Monoxide with an Internal Sensor 

 

 

 

Technical Data 

Power Supply 

230Vac –10%/+10% 50Hz 

 

Power Consumption 

2VA 

 

Contact Rating 

Sealed relay: 6(2)A @ 250Vac SPDT 

 

Indicators (LED) 

Operating: Green LED 
Alarm: Red LED 
Fail: Yellow LED 
Alarm: Buzzer (after ~15 seconds) 

 

Activation Delay 

~ 1 minute 

 

Relay Activation Delay 

~ 15 seconds 

 

Sensor Type 

Electrochemical cell 

 

Sensor Lifetime 

3 years 

 

Detected Gas 

Carbon Monoxide (CO) 

 

Protection Class 

IP40 

 

Pre-alarm Threshold 

16ppm 

±

 4ppm (20mg/m

3

 

±

 5mg/m

3

 

Main-alarm Threshold 

80ppm 

±

 20ppm (100mg/m

3

 

±

 25mg/m

3

 

Operating Temperature 

0

°

C .. +40

°

C; 20% .. 80% rH non-condensing 

 

Storage Temperature 

-10

°

C .. +50

°

 

Enclosure 

ABS V0 self-extinguishing 

 

Dimensions 

130W x 100H x 62D mm 

 

Weight 

0.5 kg  

 

RGI-CO0-L42 is designed to monitor carbon monoxide gas. The unit has 
built-in electrochemical cell for detecting toxic gases.  
 
The unit has IP40 rated enclosure and it can be wall mounted. 
 
 
FEATURES 

 

Electrochemical cell sensor 

 

230Vac supply 

 

16ppm (20mg/m3) pre-alarm, 80ppm (100mg/m3) main alarm 
threshold 

 

Test/alarm-reset button 

 
 

Отзывы: