Wiring
Instructions
The electrical installation, device connection and commissioning can only be
carried out by qualified professionals and according to the local wiring
regulations!
Make electrical wirings as indicated in Fig. 1, 2 or 3. Please note that the intervention delay is strictly
dependant both on a correct positioning of the detector in the room and to the type of gas to be detected.
In case of 'light' gases as CO an installation in high places is advisable (roughly 180 cm. from floor).
Please avoid installation in such a position that it can be directly in the stream of smokes or vapors
containing compounds which are dangerous for the sensor health (as an example: do not position the
detector in the stream of fat smokes produced by cooking).
WARNING
The appliance must be wired to the electric mains through a switch capable of disconnecting all
poles in compliance with the current safety standards and with a contact separation of at least 3
mm in all poles.
- Installation and electrical wirings of this appliance must be made by qualified technicians and in
compliance with the current standards.
- Before wiring the appliance be sure to turn the mains power off.
THE INSTALLATION OF THE DETECTOR DOESN'T EXEMPT FROM THE OBSERVANCE OF ALL
RULES ABOUT THE CHARACTERISTICS, INSTALLATIONS AND THE USE OF THE GAS DEVICES,
THE VENTILATION OF THE ROOMS AND THE EMISSIONS OF THE PRODUCTS OF THE
COMBUSTION PRESCRIBED FROM UNI STANDARDS AND THE PROVISIONS OF THE LAW.