GWF-7075 Manual —
LS10147-002GF-E:G 10/5/2022
55
Zone
Programming
Heat Detector Sensitivity
Use this feature to set the temperature at which high temperature detectors will respond. All detectors in the zone will respond in the same
way.
The range for the ATD-HL2F heat detector is from 135°F to 190°F.
The ATD-HL2Fheat detectors are absolute temperature devices. This means that they respond to an alarm immediately if the temperature in
the zone goes above the programmed temperature.
1.
Enter the temperature at which the heat detector will respond. Or use the up or down arrow keys to scroll through the range.
2.
Then press ENTER.
Smoke Detector Sensitivity
All detectors in the zone will respond as programmed in this Menu location.
1. Detectors are suitable for Open Area Protection within the listed air velocity range. Typically, this range is 0 - 4,000 ft/min for photoelectric
detectors and 0 - 1,200 ft/min for ionization detectors. Be sure to confirm this range before installing the detector by referring to the
Manufacturer’s Installation Instructions.
2. Detectors will default to Open Area Protection (High Sensitivity). Where applicable, detectors will only be compliant with UL 268 7th Edition if
they remain programmed to open area.
3. The alarm and threshold limits determined by the control unit interconnected to detectors that employ a special application
mode/configuration are designed and shipped from the factory with the Detector Sensitivity Setting set to an acceptable Open Area Protection
sensitivity being the default mode of operation.
The special application mode/configuration shall not be activated at the control unit without a deliberate action by the user to initiate the
special application mode through an alternate detector sensitivity selection setting. Additionally, the extended label should be modified at this
address to include the phrase ‘SPECIAL APPLICATIONS’ or ‘SPECIAL APPS’ for compliance with UL 864 requirements. Please refer to the
FACP Programming/Installation Instructions for further instructions on altering the extended labels.
3.
Use the up or down arrow key to scroll through the range or use the number keys on the annunciator, then press ENTER.
Zone Accessory Options
1.
Login to the panel.
2.
Select 7 to access the Program Menu.
3.
Press 2 to enter the Zone Menu.
4.
Press 1 to edit a zone.
5.
Enter the Zone Number, then press ENTER.
6.
Press 3 to edit the Zone’s Accessory options.
Single or Multi-Station cadence pattern (choose from Patterns 00 to 02, 23. See Appendix C, “Cadence Patterns”, on page 95.
CO Single and Multi-station Cadence (choose from Cadence Patterns 00 to 02, 23).
7.
For Local Zone, (choose Y or N, for Yes or No),
1
The MCS-COF and other CO detectors can only be installed in a 1 count zone. They will operate as a 1- count point regardless of the
programmed zone type (i.e. Alarm Verification, 2 count, etc.).
2
PAS operation requires the approval of the local Authority Having Jurisdiction. Alarm Verification, two-count, single interlock releasing, and
double interlock releasing cannot be used while PAS is enabled.
NOTE:
Drift compensation is automatic for all smoke detectors (photoelectric and ionization). The feature is always in effect, no programming
is required. See Section 7.3.11 for information about how to check if a detector is in UL compliance.
Type of Smoke Detector
Choices
Comments
ASD-PL2F and ASD-PTL2F Low (3.5% obscurity)
If the day/night sensitivity option is selected, you can have different sensitivity
settings during the day and at night. You can program the days of the week
that Day/Night Sensitivity will automatically adjust. You can also designate
specific days as holidays. Holiday and weekend days use night sensitivity for
the entire day.
Medium (2.5% obscurity)
High (1.5% obscurity) (Default)
DNR with ASD-PL2F and
ASD-PL2FR
Low (2.5% obscurity)
Medium (2.0% obscurity)
High (1.5% obscurity) (Default)
MCS-COF
Low (4% obscurity)
Medium (3% obscurity)
High (2% obscurity) (Default)
MCS-CO3
Fixed
Low, Medium, and High settings have no effect for CO detectors. Day and
night settings also have no effect on these detectors.
Table 6.3 Detector Sensitivity Choices
NOTE:
Automatic drift compensation is always in effect for all detectors. See Section 7.3.11 for information on the procedure to check if a
detector is in compliance.
NOTE:
The B200S Intelligent Sounder base provides the recommended CO cadence pattern
Содержание Honeywell GWF-7075
Страница 51: ...GWF 7075 Manual LS10147 002GF E G 10 5 2022 51 Notes...
Страница 98: ...Cut along dotted line...