GWF-7075 Manual —
LS10147-002GF-E:G 10/5/2022
Control Panel Installation
Telephone Connection
4.11 Telephone Connection
Connect the telephone lines as shown in Figure 4.21. Model 7860 phone cord is available from Honeywell for this purpose.
A number of programmable options are available for customizing the telephone lines. These options are described in Section 6.6.
4.12 Notification Appliance/Auxiliary Power Circuits
Two outputs are built-in to the GWF-7075 FACP which can be programmed to be used as NACs (Class A or Class B) or as aux power. This
section of the manual explains how to install conventional notification appliances and how these terminals can be used for auxiliary power.
4.12.1 Conventional Notification Appliance
This subsection of the manual explains how to install conventional notification appliances for Class A and Class B configurations.
Class B Notification Wiring
You must use an appliance from the list of compatible devices listed in the
Device Compatibility Document
, P/N: 9000-0427-L8.
To install a Class B notification appliance circuit:
1.
Wire Class B Notification appliances as shown below.
2.
Configure the circuit through programming (see Section 6.5).
.
NO
NC
C
TROUBLE
RELAY 2
C
NO
NC
RELAY 1
C
NO
NC
red
green
gray
brown
red
green
gray
brown
Figure 4.21 Connection of Telephone Lines
Model
#7860
Model
#7860
NOTE:
Where power to a device or appliance is supplied over a separate pathway from the notification appliance and/or SLC, the operation of
the power pathway shall meet the performance requirements of the, notification appliance, and/or signaling-line circuit(s) and the power circuit
shall be defined by the applicable class in the product installation wiring diagram/instructions consistent with the operation of the particular
power pathway.
NO
NC
C
TROUBLE
SLCIN
+
_
SLCOUT
SLCPROG
+
_
+
_
SBUS
A
B
+
_
NAC 1
NAC 2
+
+
+
+
+
+
Class B
supervised,
regulated NAC
circuits
shown in alarm
condition
supervised,
power-limited
NAC wiring
4.7k
Ω
EOL
Figure 4.22 Class B Notification Appliance Circuit Wiring