![Gamewell Honeywell GWF-7075 Скачать руководство пользователя страница 84](http://html1.mh-extra.com/html/gamewell/honeywell-gwf-7075/honeywell-gwf-7075_manual_3358294084.webp)
84
GWF-7075 Manual —
LS10147-002GF-E:G 10/5/2022
Reporting
Receivers Compatible with the Control Panel
Background Music Switch is Trouble
pi Exp. ID UT
Point #
UTNNXXPPPP
1
379
Exp. ID
Point #
Background Music Switch is Trouble
Restored
pi Exp. ID UJ
Point #
UJNNXXPPPP
3
379
Exp. ID
Point #
Background Music Switch is Disabled
pi Exp. ID UB
Point #
UBNNXXPPPP
1
580
Exp. ID
Point #
Background Music Switch is Enabled
pi Exp. ID UU
Point #
UUNNXXPPPP
3
580
Exp. ID
Point #
CO Detector Trouble
pi Exp. ID GT
Point #
GTNNXXPPPP
1
373
Exp. ID
Point #
CO Detector Trouble Restore
pi Exp. ID GJ
Point #
GJNNXXPPPP
3
373
Exp. ID
Point #
CO Detector Disabled
pi Exp. ID GB
Point #
GBNNXXPPPP
1
571
Exp. ID
Point #
CO Detector Enabled
pi Exp. ID GU
Point #
GUNNXXPPPP
3
571
Exp. ID
Point #
Detector Alarm
pi Exp. ID FA
Point #
FANNXXPPPP
1
110
Exp. ID
Point #
Detector Alarm restore
pi Exp. ID FH
Point #
FHNNXXPPPP
3
110
Exp. ID
Point #
Detector Disabled
pi Exp. ID FB
Point #
FBNNXXPPPP
1
571
Exp. ID
Point #
Detector Enabled
pi Exp. ID FU
Point #
FUNNXXPPPP
3
571
Exp. ID
Point #
Detector Trouble
pi Exp. ID FT
Point #
FTNNXXPPPP
1
373
Exp. ID
Point #
Detector Trouble restore
pi Exp. ID FJ
Point #
FJNNXXPPPP
3
373
Exp. ID
Point #
Detector CO Alarm
pi Exp. ID GA
Point #
GANNXXPPPP
1
162
Exp. ID
Point #
Detector CO Alarm Restore
pi Exp. ID GH
Point #
GHNNXXPPPP
3
162
Exp. ID
Point #
Detector CO Supervisory Alarm
pi Exp. ID GS
Point #
GSNNXXPPPP
1
200
Exp. ID
Point #
Detector CO Supervisory Alarm Restore
pi Exp. ID GR
Point #
GRNNXXPPPP
3
200
Exp. ID
Point #
External Reset/Silence/Fire Drill switch
disabled
pi Exp. ID UB
Point #
UBNNXXPPPP
1
571
Exp. ID
Point #
External Reset/Silence/Fire Drill switch
enabled
pi Exp. ID UU
Point #
UUNNXXPPPP
3
571
Exp. ID
Point #
External Reset/Silence/Fire Drill switch
trouble
pi Exp. ID UT
Point #
UTNNXXPPPP
1
373
Exp. ID
Point #
External Reset/Silence/Fire Drill switch
trouble restore
pi Exp. ID UJ
Point #
UJNNXXPPPP
3
373
Exp. ID
Point #
Interlock switch alarm (Water Release Zone) pi Exp. ID FA
Point #
FANNXXPPPP
1
110
Exp. ID
Point #
Interlock switch alarm restore
(Water Release Zone)
pi Exp. ID FH
Point #
FHNNXXPPPP
3
110
Exp. ID
Point #
Interlock switch disabled
pi Exp. ID FB
Point #
FBNNXXPPPP
1
571
Exp. ID
Point #
Interlock switch enabled
pi Exp. ID FU
Point #
FUNNXXPPPP
3
571
Exp. ID
Point #
Interlock switch trouble (Water Release Zone) pi Exp. ID FT
Point #
FTNNXXPPPP
1
373
Exp. ID
Point #
Interlock switch trouble restore (Water
Release Zone)
pi Exp. ID FJ
Point #
FJNNXXPPPP
3
373
Exp. ID
Point #
Manual pull switch alarm
pi Exp. ID FA
Point #
FANNXXPPPP
1
115
Exp. ID
Point #
Manual pull switch alarm restore
pi Exp. ID FH
Point #
FHNNXXPPPP
3
115
Exp. ID
Point #
Manual pull switch disabled
pi Exp. ID FB
Point #
FBNNXXPPPP
1
571
Exp. ID
Point #
Manual pull switch enabled
pi Exp. ID FU
Point #
FUNNXXPPPP
3
571
Exp. ID
Point #
Manual pull switch trouble
pi Exp. ID FT
Point #
FTNNXXPPPP
1
373
Exp. ID
Point #
Manual pull switch trouble restore
pi Exp. ID FJ
Point #
FJNNXXPPPP
3
373
Exp. ID
Point #
Manual release switch alarm
(Water Release Zone)
pi Exp. ID FA
Point #
FANNXXPPPP
1
110
Exp. ID
Point #
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier
SIA
Event Description
Module ID
# (If Any)
SIA
Event
Codes
Parameter
Fixed Length
Format NN - panel
ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier Event
Code
Group #
Contact #
Table 8.2 Reporting Formats Table (Continued)
Содержание Honeywell GWF-7075
Страница 51: ...GWF 7075 Manual LS10147 002GF E G 10 5 2022 51 Notes...
Страница 98: ...Cut along dotted line...