66
GWF-7075 Manual —
LS10147-002GF-E:G 10/5/2022
Programming
JumpStart Auto-Programming
Then, press ENTER two times to make your selection and exit.
6.6.7 Edit Banner
The banner is the message that displays on the panel LCD when the system is normal. For example, a system is normal when no alarms or
troubles exist and no one is currently using the system menus. You can create a custom message, which can be up to 40 characters, two lines
of 20 characters each. If you do not create a custom message, the system will use the internal banner. You cannot change the internal banner.
To customize the banner display message, do the following.
1.
Login to the panel.
2.
Select 7 to access the program menu.
3.
Select 5 to access System Options.
4.
Select 7 for Edit Banner.
5.
To select each character of a word, press the up or down arrow. Then, press the right arrow key to move to the next character.
6.
After you enter the word or the sentence, press ENTER to move the cursor to line two of the custom banner.
6.6.8 SLC Family
The GWF-7075supports Velociti SLC devices.
1.
Login to the panel.
2.
Select 7 to access the program menu.
3.
Select 5 to access System Options.
4.
Select 8 for SLC Family. The type, “Velociti” displays.
6.7 JumpStart Auto-Programming
The FACP supports an incremental JumpStart.
For example, after the initial JumpStart
and customization, if you add more devices and per-
form JumpStart again, the additional devices are added. You will not lose any of your previous custom programming.
To run JumpStart auto-programming:
1.
Login to the panel.
2.
Select 7 to access the program menu.
3.
Select 6 to access JumpStart Auto-Programming.
4.
From the Warning screen, press the up or down arrow to select “Yes”.
5.
Press ENTER.
6.8 Restore Defaults
This option allows you to restore the panel to its factory default settings. All programming will be lost.
1.
Login to the panel.
2.
Select 7 to access Panel Programming.
3.
Select 7 for Restore Defaults.
4.
From the Warning screen, press the up or down arrow keys to select YES. Then, press ENTER.
NOTE:
See Appendix A for instructions on how to edit the banner.