8
GWF-7075 Manual —
LS10147-002GF-E:G 10/5/2022
Section 1: Introduction
The GWF-7075 and GWF-7075BFire Alarm Control / Communicators are Addressable Fire Alarm Control Systems that meets the require-
ments of UL 864 10th Edition Standard.
1.1 Basic System Overview
1.1.1 Hardware Features
•
The GWF-7075 has one built in signaling line circuit (SLC) that supports 75 Velocitidetectors and 75 Velocitimodules.
•
The GWF-7075 is capable of outputting 2.5A of output power during an alarm activation through 2 sets of terminals for the notification
appliance circuits or an auxiliary application. Each circuit is power-limited and can source up to 2.5A during an alarm activation. The
constant auxiliary power load must not exceed 1A for normal standby.
•
Built-in dual phone line, digital alarm communicator/transmitter (DACT), IP, or optional cellular technologies.
•
Reports events to central station by point or by zone.
•
UL Listed for pre-action and deluge releasing systems.
•
Two general purpose Form C programmable relays.
•
One Form C Trouble Relay.
•
Basic system operation can be performed from the onboard, or any remote annunciator.
•
Up to 20 user profiles can be programmed, each having custom Access Code, and Main Menu items.
•
Can be used with any combination of up to 8 Model RA-1000 or RA-1000R Remote LCD Annunciators (sold separately).
•
Can be used with model 5880 for a total of eight devices on one control panel. See Section 4.9 for additional information on these
models.
•
Printing of event log available through the Model 5824 serial/parallel printer interface module.
•
125 software zones, 125 Output Groups.
•
Add four Notification/Auxiliary power circuits with each GFPS-6S NAC Expander. See note below.
1.1.2 Software Features
•
Advanced smoke detector features:
– Automatic drift compensation
– Maintenance alert region
– Point status meets calibrated smoke test requirements for NFPA 72
•
“JumpStart” feature for easy programming
•
Non-volatile event history stores 1000 events
•
A choice of output patterns available for notification outputs, including Temp 4 along with ANSI 3.41 temporal signal
•
Built-in synchronization appliance support for AMSECO, Gentex, Wheelock, or System Sensor
1.2 About this Manual
This manual is intended to be a complete reference for all installation and operation tasks for the GWF-7075.
1.2.1 Terms Used in this Manual
The following terminology is used with the GWF-7075 system:
NOTE:
All references to GWF-7075 within this manual are applicable to the GWF-7075 and GWF-7075B.
NOTE:
Total output power for both circuits must not exceed 2.5A in alarm condition, and total output power for both circuits must not exceed
1.0A for all other activation conditions (i.e. Supervisory, Trouble, etc.).
NOTE:
The system can support a maximum of eight intelligent power modules.
Term
Description
SLC
Signaling Line Circuit
Module
The term module is used for all hardware devices except for SLC addressable devices and notification
appliances. This includes the GWF-7075 panel itself.
Input Point
An addressable sensing device, such as a smoke or heat detector or a contact monitor device.
Input Zone
A protected area made up of input points.
Output Point (or Output Circuit)
A notification point or circuit for notification appliances. Relay circuits and auxiliary power circuits are also
considered output points.
Group (or “Output Group”)
A group of output points. Operating characteristics are common to all output points in the group.
Output (or “Cadence”) Pattern
The pattern that the output will use, for example, Constant, March Code, ANSI 3.41. Applies to zones
and special system events. See Appendix D for additional information.
Mapping
Mapping is the process of specifying which outputs are activated when certain events occur in the
system. Figure 5.2 describes mapping in detail.
SWIFT
Smart Wireless Integrated Fire Technology
Table 1.1 Manual Terminology
Содержание Honeywell GWF-7075
Страница 51: ...GWF 7075 Manual LS10147 002GF E G 10 5 2022 51 Notes...
Страница 98: ...Cut along dotted line...