GWF-7075 Manual —
LS10147-002GF-E:G 10/5/2022
Programming Overview
Mapping Overview
Circuits 1-2
Configured as Notification and assigned to Group 1. JumpStart auto-programming automatically programs Zone 1 to activate
Group 1 using constant on output when an alarm condition occurs.
Circuit 3 (Relay 1)
Assigned to Group 124. JumpStart auto-programming automatically programs Zone 1 to activate Group 124 using con-
stant on output when a supervisory condition occurs.
Circuit 4 (Relay 2)
Assigned to Group 125. JumpStart auto-programming automatically programs Zone 1 to activate Group 125 using con-
stant on output when an alarm occurs.
Addressable output points (Relay modules)
All addressable relay devices will be configured as “Output Pt” (general purpose output
point) and assigned to Group 1.
5.2.3 Running JumpStart Auto-Programming
Run JumpStart auto-programming immediately after you address and connect all the input devices (detectors, pull stations, and so on) and
output devices (notification appliances, relays, and so on).
To run JumpStart auto-programming:
11. Login to the panel and access the main menu.
12. Select 7 for the Program Menu.
13. From the next Menu, select 6 for JumpStart.
14. The message, “SLC FAMILY VELOCITI” appears. press ENTER.
15. A series of messages display for the next several seconds. JumpStart scans the SLC loops for the devices. This process can take several
minutes, depending on the number of devices attached.
16. When the message “Configuring System Done” displays, press any key to continue.
17. Select one of the following options from the menu that displays.
5.3 Mapping Overview
Mapping is an important concept with the control panel. In general terms, mapping is assigning or linking events to outputs that should acti-
vate when events occur. You do this by assigning input points to input zones, output points to output groups and then linking or mapping
zones and output groups.
NOTE:
The Relay output is constant even if the zone activating the relay is programmed with an output pattern.
NOTE:
To install a few devices manually after running JumpStart, see Section 6.2.2.
Menu Options
Description
1 - Review System
Press 1 if you need to review the JumpStart
configuration.
2 - Repeat JumpStart Press 2 if you need to rerun JumpStart for any reason.
3 - Accept Changes
1.
If you are ready to make the JumpStart configuration permanent, select 3.
2.
The system will prompt you if the installation contains any addressable duct detectors used. If there are none,
select 2 for No and skip to step 8. If the system contains duct detectors, select 1 for Yes and continue with Step 3.
3.
From the list that displays, select the SLC that contains the duct detectors.
4.
The first photoelectric or ionization detector on the system will display. Select 1 for DUCT and 2 for NonDUCT.
5.
Press the up arrow key to select the next detector. Select 1 for DUCT and select 2 for NonDUCT. Continue until you
have selected all duct detectors. (Note: Press the down arrow key to move the cursor backwards through the list).
6.
When you reach the last detector on this device, press the left arrow key.
7.
The system will ask you if there are any duct detectors used. If there are, select 1 for Yes and the message, “Have
All Addressable Duct Detectors Been Identified?” prompts. Press the left arrow key to select “No” or press the right
arrow key to select “Yes”. If there are no more duct detectors, continue to Step 8.
8.
The system will restart with the saved JumpStart configuration.
9.
After the system resets, it will use the new JumpStart configuration.
4 - Discard Changes
If you want to discard the changes, and keep the configuration you had before running this JumpStart, press 4.
Table 5.1 JumpStart Menu Options