GWF-7075 Manual —
LS10147-002GF-E:G 10/5/2022
Agency Listings, Approvals, and Requirements
Underwriters Laboratories (UL)
2.2.6 Requirements for the Installation of Carbon Monoxide (CO) Detection and Warning
Equipment, NFPA 72
When using carbon monoxide detection the system must be monitored by a Supervising Station with emergency response, both aspects meet-
ing the Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment, NFPA 72.
2.2.7 NFPA Requirements
The following is the minimum configuration necessary to comply with the NFPA requirements.
Model/Module
Description
Local Releasing
Remote
Station
Auxiliary
Central
Station
Emergency
Signaling
GWF-7075
Control Unit
Y
Y
Y
Y
Y
Y
5220
Direct Connect Module
N
N
N
Y
N
O
GFPS-6S
NAC Expander
O
Y*
O
O
O
O
5880
LED I/O Module
O
O
O
O
O
O
RA-1000/R
LCD Annunciator
O
O
O
O
O
O
HWF2A-COM
Communicator
N
N
Y
N
Y
N
HWF2V-COM
Communicator
N
N
Y
N
Y
N
Y = YES, N = NO, O = OPTIONAL
Note:
Y * = You must include the GFPS-6Sfor releasing purposes.
Table 2.1 NFPA Requirement for Minimum System Configuration for GWF-7075