GWF-7075 Manual —
LS10147-002GF-E:G 10/5/2022
71
Basic Operation
System Operation
If you do not end the Walk Test manually within four hours, it will end automatically. If there is an alarm or pre-alarm condition in the sys-
tem, you will not be able to enter the Walk Test.
7.3.7 Conduct a Communicator Test
1.
From the main menu, press 1 to access System Tests.
2.
Select 5 to access Communicator Test.
The screen will display “Manual Communicator Test started”. When the test is completed, you will be returned to the Test Menu. A
manual communicator test requires that at least one daily test in the network be enabled in communicator programming.
3.
The manual communicator test will be communicated on both phone lines and Ethernet/cellular paths if they are all programmed. Each
manual communicator test will alternate between one of the phone line paths and one of the AlarmNet paths.
7.3.8 Manual AlarmNet Registration
1.
From the main menu, press 1 for System Tests.
2.
Select 8 to access Register AlarmNet. The screen will display and ask for confirmation. Feedback will be given if the command was
sent or not.
7.3.9 Silence Alarms or Troubles
1.
When an alarm is sounding, press SILENCE and enter your code or rotate the key at the prompt.
If an external silence switch was installed, activating the switch will silence alarms or troubles.
If you are actively using the system menus when you press SILENCE, you do not need to enter your code or rotate the key.
7.3.10 Reset Alarms
Press RESET and enter your code or rotate the key at the prompt. If an external reset switch was installed, activating the switch will reset the
alarms.
Reset Communicator
This options allows the user to reset the communicator. The LCD will display, “Communicator Reset in progress… Please Wait”. You will be
returned to the main menu when the reset is complete.
The communicator is not allowed to be reset when alarms or supervisories are active. Communicator reset is not allowed if any of the follow-
ing events are active:
•
Fire Alarm
•
Fire Supervisory
•
Fire Pre-Alarm
•
CO Alarm
•
CO Supervisory
7.3.11 Check Detector Sensitivity Through Point Status
The control panel constantly monitors smoke detectors to ensure that sensitivity levels are in compliance with NFPA 72.
If the sensitivity for a detector is not in compliance, the panel goes into trouble, generating a CAL TRBLE condition. A detector enters a
CAL MAINT state to indicate that it is approaching an out of compliance condition (but is currently still in compliance).
When a CAL TRBLE condition occurs, the Central Station receives a detector trouble report (“373” and the zone or point for Contact ID for-
mat; “FT” and the zone or point in SIA format). To check the sensitivity for an individual detector, follow the steps below:
1.
From the main menu, press 2 to access Point Functions.
2.
Press 2 to access Point Status.
3.
Select the desired module.
4.
Enter the number of the desired point and press ENTER.
5.
A screen similar to those shown below will display.
NOTE:
The panel does not do a full 30 second reset on resettable power outputs. As soon as the device is back to normal, the panel is ready
to access the next device.
NOTE:
Alarm and trouble signals that were silenced will resound every 4 or 24 hours, depending on user programming, until the trouble is
cleared.
Содержание Honeywell GWF-7075
Страница 51: ...GWF 7075 Manual LS10147 002GF E G 10 5 2022 51 Notes...
Страница 98: ...Cut along dotted line...