Point
Programming
5.
Enter the group number, then press ENTER..
6.4.3 Edit Output Group Template
1.
Login to the panel. The panel will automatically access the Main Menu.
2.
Select 7 to access the Panel Programming.
3.
Press 3 to enter the Group Menu.
4.
Press 3 to edit the OPG Template.
5.
Enter the Template number, then press ENTER.
6.
On the Template name, press ENTER to edit the name.
You can enter a description to assign and display a descriptive name for a group.
7.
Press the right arrow to access the output group and select Yes or No to select which output group to include in the template.
6.5 Point
You may need to change the characteristics of the individual input points (detectors and switches) even after using JumpStart Auto-Program-
ming. This section describes how to change the options for the following:
•
point type
•
latching/non-latching
•
silenceable/non-silenceable
•
zone assignment (input points)
•
detector accessory base options
•
point name
•
group assignment (output points)
6.5.1 Point Programming for SLC
To program for points, follow these steps:
1.
Login to the panel.
2.
Select 7 to access the Program menu.
3.
Press 4 to enter the Point menu.
4.
Press the up or down arrows to select the desired module. Refer to Section 5.6, “Programming Menu Quick Reference” for available
choices.
5.
Enter the number of the desired point, then press ENTER.
6.
To select the type of device, press the up or down arrows keys. Refer to Table 6.4 under the column heading “Type Selection” for a list
of choices.
Group: G91 of 8
Point: 98:001
Number: 1 of 8
Figure 6.5 View Group Points
NOTE:
See Appendix A for information to edit names.
Type
Selection
Function
Latching
Option
Comments
UNUSED
DETECTOR
PHOTO
PHOTO-HEAT
ION
HEAT
PHOT DUCT
2WIRE SMK
ACCLIMATE
HEAT HT
BEAM
Table 6.4 Point Programming for Internal SLC Module