GWF-7075 Manual —
LS10147-002GF-E:G 10/5/2022
95
Appendix C: Cadence Patterns
Table C.1 shows the cadence patterns available for use with the control panel.
#
Name
Pattern Description (Patterns repeat until condition is cleared.)
00
Constant
Continuous sound (This is the only pattern that can be used for relay circuits. The system will
override any other choice.)
01
March Time
0.5 second on, 0.5 second off
02
ANSI 3.41
0.5 sec on, 0.5 sec off, 0.5 sec on, 0.5 sec off, 0.5 sec on, 1.5 sec off
03
Single Stroke
0.1 sec on, 1 sec off, 0.1 sec on, 1 sec off, 0.1 sec on, 3 sec off
04
California
5 sec on, 10 sec off
05
Zone-coded, Zone 1
0.5 sec on, 0.5 sec off
This pattern is multiplied by the zone number in alarm, followed by 3 seconds off.
For example, Pattern 6, Zone 2 coded: (pattern x two):
0.5 sec on, 0.5 sec off, 0.5 sec on, 0.5 sec off, 3 sec off
06
Zone-coded, Zone 2
07
Zone-coded, Zone 3
08
Zone-coded, Zone 4
09
Zone-coded, Zone 5
10
Zone-coded, Zone 6
11
Zone-coded, Zone 7
12
Zone-coded, Zone 8
13
Zone-coded, Custom 1
14
Zone-coded, Custom 2
15
Zone-coded, Custom 3
16
Zone-coded, Custom 4
17
Sync Type- Faraday (N/A)
These outputs provide synchronization for Gentex, System Sensor, Wheelock, or AMESECO
synchronized appliances.
18
Sync Type- Gentex
19
Sync Type- System Sensor
20
Sync Type- Wheelock
21
Sync Type- AMSECO
22
Power Isolated
Disconnected. No voltage at terminals.
23
Temporal 4
0.1 sec on, 0.1 sec off, 0.1 sec on, 0.1 sec off, 0.1 sec on, 0.1 sec off, 0.1 sec on, 5 sec off,
Table C.1 Cadence Patterns
Содержание Honeywell GWF-7075
Страница 51: ...GWF 7075 Manual LS10147 002GF E G 10 5 2022 51 Notes...
Страница 98: ...Cut along dotted line...