PULSE Installation, Commissioning and Servicing Manual - Revision 19
Entering Service Mode
Hold FILL 3 seconds, enter Password,
press FILL again
Use 2 and 8 to scroll between items
Use 4 and 6 to scroll between options
Pressing 5 changes setting, turns on/off
FILL = Enter
Press CLR 3 seconds to exit
1 2 3
4 5 6
7 8
9
C
0
FILL
Hose 1
front nozzle
switch open
POS ENABLED
(for standalone)
Comms must be isolated for standalone
At POS MENU press FILL
Press 8 till you see ENABLED, Press 5 to change to NO
Press 4 or 6 to scroll fuelpoints, set to NO
POS will re-enable when cable is re-connected
Set Price
Only works once in Standalone (no comms, POS set
to OFF)
At PRICE GRADE1, press FILL, enter price, FILL
Press 6 for PRICE GRADE2, etc.
Repeat on each display
Set Timeouts
At TIMEOUT MENU press FILL, press 6 to choose item
Press FILL, enter time in seconds, press FILL to set
Set Start Delay
At STARTDEL MENU press FILL, press 6 to choose hose
Press FILL, enter time in seconds, press FILL to set
Enter 55 for 5.5 seconds
Set Hoses Active
At HOSE MENU
Press 5 to change, 0 = OFF 1 = ON
Press 6 to move to the next hose
VR Control Active/Inactive
At VR2 Menu
Press 5 to change. Press 6 for ATPM.
Hose Mapping
At MAPPING MENU press FILL, enter order, Press FILL
Press 6 to move to the next fuelpoint
Set Time/Date
Scroll to Time or Date
Press FILL, enter complete time/date
Setting Flow Control
At FLOWCTRL press FILL
Press FILL to edit, enter target in LPM, eg: 38, press FILL
Press 5 to turn Flow Control on/off
Press 6 for next hose
Set for all hoses on all fuelpoints as required
Do not set LPG or ULTRA hoses
M010
V**0010
L
$
Checking Inputs
At STK MENU, press FILL, then press 8 to view INPUTS
Lifting each nozzle opens the switch 0 = OFF 1 = ON
Checking Outputs (Stack Test Motors and Valves)
Comms must be isolated to view STK Menu
At STK MENU, press FILL to CONTROL OUTPUTS
Press FILL at CONTROL OUTPUTS for Motor and Valve
control
Use keys 2,4,6,8 to move around
Use the 5 key to turn M and V on/off
0 = off/valve closed 1 = on/valve open
M: The 1st 0 = grade 1 motor, etc.
V: The 1st 0 = grade 1 front valve
V: The 2nd 0 = grade 1 rear valve
V: The 3rd 0 = grade 2 front valve, etc.
Change pump numbers, FPID
At FP ID Menu
Press FILL, enter the pump number, press FILL to set
Scroll using keys 4 or 6 to other fuelpoints and repeat
5/6 Digit Setting
Press FILL at POS MENU. Press 2 till you see 5/6 DIGIT
Press 5 to change, press 6 for other fuelpoints
Firmware upgrade
New Firmware must be on SD card in Firmware folder
Insert and unlock SD card
Scroll to FIRMWARE
Display shows the current installed version
Press 4 or 6 to select item to upgrade
Press 5, then 5 to start, BUSY is displayed
Wait, then check new version is showing
Repeat for all firmware items to be upgraded
INPUTS
1000000000
L
$
Edit mode
Shut Open
Off
On
38
Window
Hose 1
C
FC FP7
H1 OFF
L
$
22
QUICK REFERENCE GUIDE - VERSION 1�20