Chapter 4 Connecting Cables
4.5 Power Cord Connection
FUJITSU Storage ETERNUS DX60 S2 Disk storage system User’s Guide -Installation-
77
Copyright 2014 FUJITSU LIMITED
P3AM-5502-05ENZ0
Procedure
1
Remove the power cord clamp from the power distribution unit.
Loosen the two thumb screws on both sides of the power cord clamp to remove it.
2
Connect the power distribution unit outlets and power supply unit inlets with the
power cords (AC output cables, 3m) provided with the power distribution unit.
The procedures to connect the power supply unit is same as the
in
Power Distribution Units are Installed" (page 72)
The following figure shows a connection diagram of AC outlet cables.
●
For Power distribution unit for ETERNUS DX Disk storage system (2U, Max 6
enclosures connection)
IMPORTANT
Each enclosure has two power supply units (PSU#0 and PSU#1).
The power cords must be connected to the inlets of both power
supply units.
Power cord clamp
Thumb screw
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
Drive Enclosure
Controller Enclosure
Power distribution
unit A
Power distribution
unit B
PSU#0
Inlet
PSU#1
Inlet
PSU#1 Inlet
PSU#0 Inlet
: Connect between the OUTn of the power distribution unit A
and the PSU#0 inlets of the ETERNUS DX Disk storage
: Connect between the OUTn of the power distribution unit B
and the PSU#1 inlets of the ETERNUS DX Disk storage