2-32. E: AC.X. Heat sink temperature error (Outdoor unit)
Indicator
Indoor unit
Operation indicator
10 time flash
Timer indicator
12 time flash
Economy indicator
Continuous flash
Error code
E: AC
outdoor unit
"Error code table (Outdoor unit)"
Detective actuator
Outdoor unit inverter PCB
Protection stop by heat sink temperature ≥ 176 °F
(80 °C) during heat sink operation generated 2 times
within 24 hours.
Heat sink temperature thermistor
Forecast of cause
Foreign matter on heat sink, heat sink dirty
Foreign matter on heat exchanger, excessive ambient
temperature rise
Heat sink temp. thermistor defective
Check point 1. Check the heat sink state
Heat sink foreign matter, soiling check
Check point 2. Check the foreign matter and ambient temperature of heat exchanger
•
Heat exchange foreign matter check
•
Ambient temperature not raised by effect of other heat sources?
•
Discharged air not sucked in?
Check point 3. Check the heat sink temperature thermistor
The heat sink temperature thermistor characteristics check. (Check by disconnecting thermistor
from PCB.)
NOTE:
For the characteristics of the thermistor, refer to
"Thermistor resistance values"
Check point 4. Replace inverter PCB
Replace inverter PCB
End
2-32. E: AC.↓. Heat sink temperature error (Outdoor unit)
- (03-51) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Содержание AOUH18LMAS1
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 11 01 SR_CH01_AS052EF_01 ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 11 17 SR_CH02_AS052EF_04 ...
Страница 39: ...3 TROUBLESHOOTING 2021 11 17 SR_CH03_AS052EF_01 ...
Страница 42: ......
Страница 135: ...4 CONTROL AND FUNCTIONS 2021 11 17 SR_CH04_AS052EF_01 ...
Страница 138: ......
Страница 173: ...5 FILED WORKING 2021 11 17 SR_CH05_AS052EF_01 ...