2-14. E: 58.X. Intake grille error (Indoor unit)
Indicator
Indoor unit
Operation indicator
5 time flash
Timer indicator
8 time flash
Economy indicator
Continuous flash
Error code
E: 58
Outdoor unit
"Error code table (Outdoor unit)"
Detective actuator Indoor unit main PCB
→hen the Micro switch is detected open while running
the compressor.
Micro switch
Forecast of cause
Micro switch failure
Shorted connector/wire
Main PCB failure
Check point 1. Check limit switch
•
Check operation of Micro switch. (any blocking by dust, etc.)
•
Remove Micro switch and check ON/OFF switching operation by using a meter.
-> If micro switch is detective, replace it.
Check point 2. Check connector (CN11)/wire
Check loose contact of CN11/shorted wire (pinched wire).
-> Replace micro switch if the wire is abnormal
Check point 3. Replace main PCB
If Check Point 1 and 2 do not improve the symptom, change main PCB.
End
2-14. E: 58.↓. Intake grille error (Indoor unit)
- (03-29) -
2. Troubleshooting with error code