Available Sensor ID
Sensor ID
Item
Unit
Remarks
00
057
Limit switch 3 (For left filter) On/Off
08: On/Off
0: Off, 1: On
00
070
Current sensor
09: A
00
080
Indoor unit total energized hours
11: h
00
081
Total filtering hours
11: h
00
082
Indoor unit fan total operation hours
11: h
00
083
Indoor unit fan 2 total operation hours
11: h
00
084
Indoor unit fan 3 total operation hours
11: h
00
090
Temperature sensor
12: %
00
095
Presence or absence detected by
human sensor
00: —
0: Absence, 1: Presence
—: Human sensor error or No human
sensor
00
140
Operation or Stop (External input)
00: —
0: Off, 1: On
—: →hen the function setting 46 is
not set
NOTE:
Available only for external
input port of the indoor unit
00
141
Emergency stop (External input)
00: —
0: Off, 1: On
—: →hen the function setting 46 is
not set
NOTE:
Available only for external
input port of the indoor unit
00
142
Forced stop (External input)
00: —
0: Off, 1: On
—: →hen the function setting 46 is
not set
NOTE:
Available only for external
input port of the indoor unit
00
143
Operation or Stop 2 (External input)
00: —
0: Off, 1: On
—: →hen the function setting 46 is
not set
NOTE:
Available only for external
input port of the indoor unit
00
144
External thermostat off (External
input)
00: —
0: Off, 1: On
00
145
Cooling operation on (External input)
00: —
0: Off, 1: On
00
146
Cooling operation off (External
output)
00: —
0: Off, 1: On
NOTE:
The value is output even if
the function setting or
rotary switch is not set.
00
155
Operation or Stop On/Off (External
output)
00: —
0: Off, 1: On
NOTE:
The value is output even if
the function setting or
rotary switch is not set.
00
156
Error On/Off (External output)
00: —
0: Off, 1: On
NOTE:
The value is output even if
the function setting or
rotary switch is not set.
00
157
Indoor unit fan interlocking On/Off
(External output)
00: —
0: Off, 1: On
NOTE:
The value is output even if
the function setting or
rotary switch is not set.
00
158
Cooling thermostat On/Off (External
output)
00: —
0: Off, 1: On
NOTE:
The value is output even if
the function setting or
rotary switch is not set.
00
159
Requested cooling strength On/Off
(External output)
00: —
0: Off, 1: On
NOTE:
The value is output even if
the function setting or
rotary switch is not set.
7-14. Unit status monitoring and the detected value indication
- (04-28) -
7. Various control
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
Содержание AOUH18LMAS1
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 11 01 SR_CH01_AS052EF_01 ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 11 17 SR_CH02_AS052EF_04 ...
Страница 39: ...3 TROUBLESHOOTING 2021 11 17 SR_CH03_AS052EF_01 ...
Страница 42: ......
Страница 135: ...4 CONTROL AND FUNCTIONS 2021 11 17 SR_CH04_AS052EF_01 ...
Страница 138: ......
Страница 173: ...5 FILED WORKING 2021 11 17 SR_CH05_AS052EF_01 ...