2-12. E: 42.X. Indoor unit heat exchanger sensor error (Indoor
unit)
Indicator
Indoor unit
Operation indicator
4 time flash
Timer indicator
2 time flash
Economy indicator
Continuous flash
Error code
E: 42
outdoor unit
"Error code table (Outdoor unit)"
Detective actuator
Indoor unit main PCB
→hen heat exchanger temperature thermistor open or
short circuit is detected.
Heat exchanger temperature
thermistor
Forecast of cause
Connector connection failure
Thermistor failure
Main PCB failure
Check point 1. Check connection of connector
•
Check if connector is loose or removed.
•
Check erroneous connection.
•
Check if thermistor cable is open
-> Reset power when reinstalling due to removed connector or incorrect wiring.
Check point 2. Remove connector and check thermistor resistance value
•
For the heat exchanger thermistor resistance value, refer to
•
If thermistor is either open or shorted, replace it and reset the power.
Check point 3. Check voltage of main PCB
Make sure circuit diagram of each indoor unit and check terminal voltage at thermis-
tor (DC 5.0 V).
NOTE:
For details of thermistor connector, refer to
TECHNICAL DATA AND PARTS LIST on page 02-18.
If the voltage does not appear, replace main PCB.
End
2-12. E: 42.↓. Indoor unit heat exchanger sensor error (Indoor unit)
- (03-27) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Содержание AOUH18LMAS1
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 11 01 SR_CH01_AS052EF_01 ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 11 17 SR_CH02_AS052EF_04 ...
Страница 39: ...3 TROUBLESHOOTING 2021 11 17 SR_CH03_AS052EF_01 ...
Страница 42: ......
Страница 135: ...4 CONTROL AND FUNCTIONS 2021 11 17 SR_CH04_AS052EF_01 ...
Страница 138: ......
Страница 173: ...5 FILED WORKING 2021 11 17 SR_CH05_AS052EF_01 ...