2-24. E: 86.X. High pressure switch error (Outdoor unit)
Indicator
Indoor unit
Operation indicator
8 time flash
Timer indicator
6 time flash
Economy indicator
Continuous flash
Error code
E: 86
outdoor unit
"Error code table (Outdoor unit)"
Detective actuator Outdoor unit main PCB
→hen pressure switch open is detected in 10 seconds
after the power is turned on.
High pressure switch
Forecast of cause
High pressure switch connector disconnection or open
High pressure switch characteristics failure
Main PCB failure
Check point 1. Check the high pressure switch connection state
•
Check connector and wiring connection state.
•
Check if cable is open
-> Reset power when reinstalling due to removed connector or incorrect wiring.
Check point 2. Check the high pressure switch characteristics
•
Check switch characteristics.
For the characteristics of the high pressure switch, refer to below.
Check point 3. Replace main PCB
Change main PCB and check operation again.
End
• Type of contact
C
H
Pressure
• Characteristics of pressure switch
Pressure switch 1
Contact: Short Open
4.2 ±0.1 MPa
Contact: Open Short
3.2 ±0.15 MPa
18/24 model: P770
2-24. E: 86.↓. High pressure switch error (Outdoor unit)
- (03-39) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Содержание AOUH18LMAS1
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 11 01 SR_CH01_AS052EF_01 ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 11 17 SR_CH02_AS052EF_04 ...
Страница 39: ...3 TROUBLESHOOTING 2021 11 17 SR_CH03_AS052EF_01 ...
Страница 42: ......
Страница 135: ...4 CONTROL AND FUNCTIONS 2021 11 17 SR_CH04_AS052EF_01 ...
Страница 138: ......
Страница 173: ...5 FILED WORKING 2021 11 17 SR_CH05_AS052EF_01 ...