1-2. Heating operation
A sensor (room temperature thermistor) built in indoor unit body will usually perceive difference or
variation between setting temperature and present room temperature, and controls operation rota-
tion number of compressor.
• If the room temperature is 11 °F (6.0 °C) lower than a set temperature, the operation rotation num-
ber of compressor will attain to maximum performance.
• If the room temperature is 2 °F (1.0 °C) higher than a set temperature, the compressor will be
stopped.
• →hen the room temperature is within the range of +2 °F (1.0°C) to -11 °F (6.0°C) of the setting
temperature, the rotation number of compressor is controlled within the range shown below.
•
Rotation number of compressor range
Unit: rps
Model name
Minimum frequency
Maximum frequency
ASUH18LMAS
ASUH24LMAS
10
130
1-3. Dry operation
The rotation number of compressor shall change according to the temperature, set temperature, and
room temperature variation which the room temperature sensor of the indoor unit has detected as
shown in the table below.
Zone is defined by set temperature and room temperature.
•
Rotation number of compressor range
Unit: rps
Model name
Outdoor temperature zone
Operating frequency
ASUH18LMAS
↓ zone
22
J zone
18
↔ zone
0
ASUH24LMAS
↓ zone
46
J zone
24
↔ zone
0
•
Compressor control based on room temperature
Ts+1°F
(Ts+0.5°C)
Ts-3°F
(Ts-1.5
°C)
Ts+3°F
(Ts+1.5
°C)
X zone
J zone
Y zone
Room temperature drops
Room temperature rises
Ts: Set temperature
Ts-1°F
(Ts-0.5°C)
1-2. Heating operation
- (04-3) -
1. Rotation number control of compressor
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
Содержание AOUH18LMAS1
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 11 01 SR_CH01_AS052EF_01 ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 11 17 SR_CH02_AS052EF_04 ...
Страница 39: ...3 TROUBLESHOOTING 2021 11 17 SR_CH03_AS052EF_01 ...
Страница 42: ......
Страница 135: ...4 CONTROL AND FUNCTIONS 2021 11 17 SR_CH04_AS052EF_01 ...
Страница 138: ......
Страница 173: ...5 FILED WORKING 2021 11 17 SR_CH05_AS052EF_01 ...