7-13. Peak cut operation
The current value is limited to reduce the power consumption by external input.
Peak cut level
Level 1
Level 2
Level 3
Level 4
Peak cut for rated capacity
Forced thermostat
off
50%
75%
100%
NOTES:
• During defrost operation, peak cut operation becomes invalid.
• Even during the peak cut operation, the operations of current overload, economy, and low noise
are effective and the outdoor unit operates by lowest current of them.
7-14. Unit status monitoring and the detected value indication
The wired remote controller can monitor the indoor and outdoor units' status and display the detect-
ed result as a relevant ID.
For details of the display method, refer to the Chapter of “Display Sensor Values” in the
Installation
Manual
of →ired remote controller (Touch panel).
The status can be monitored and displayed on the wired remote controller by assigning an arbitrary
ID. For available ID list, refer to the table below.
NOTE:
Operating time for each part cannot be reset when the part is replaced. Take notes of the
operating time before replacing to count the operating time of the replaced part.
Available Sensor ID
Sensor ID
Item
Unit
Remarks
00: Indoor unit
00
000
Suction temp.
01: °F or °C
00
001
Room temp.
01: °F or °C
→hen the wired remote controller
thermistor is enabled, temperature of
the wired remote controller thermistor
is displayed.
00
002
→ired remote controller detected
temp.
01: °F or °C
00
003
→ireless remote controller detected
temp.
01: °F or °C
Temperature detected by wireless
remote controller
00
004
Discharge air temp.
01: °F or °C
00
005
Heat exchanger inlet temp.
01: °F or °C
00
006
Heat exchanger middle temp.
01: °F or °C
00
007
Heat exchanger outlet temp.
01: °F or °C
00
020
Fan rotation number
03: rpm
00
021
Fan 2 rotation number
03: rpm
00
022
Fan 3 rotation number
03: rpm
00
030
Expansion valve
05: pls
00
040
Operating pulse for right filter
05: pls
00
041
Operating pulse for left filter
05: pls
00
042
Operating pulse for filter brush
05: pls
00
050
Power relay for outdoor unit On/Off
08: On/Off
0: Off, 1: On
00
051
Float switch On/Off
08: On/Off
0: Off, 1: On (→hen the water level
rises)
00
052
Drain pump On/Off
08: On/Off
0: Off, 1: On
00
053
Solenoid valve for reheat operation
On/Off
08: On/Off
0: Off (Opened), 1: On (Closed)
00
054
Air cleaner status On/Off
08: On/Off
0: Off, 1: On
00
055
Limit switch 1 (For grille) On/Off
08: On/Off
0: Off, 1: On
00
056
Limit switch 2 (For right filter) On/Off
08: On/Off
0: Off, 1: On
7-13. Peak cut operation
- (04-27) -
7. Various control
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
Содержание AOUH18LMAS1
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 11 01 SR_CH01_AS052EF_01 ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 11 17 SR_CH02_AS052EF_04 ...
Страница 39: ...3 TROUBLESHOOTING 2021 11 17 SR_CH03_AS052EF_01 ...
Страница 42: ......
Страница 135: ...4 CONTROL AND FUNCTIONS 2021 11 17 SR_CH04_AS052EF_01 ...
Страница 138: ......
Страница 173: ...5 FILED WORKING 2021 11 17 SR_CH05_AS052EF_01 ...