2-27. E: 95.X. Compressor motor control error (Outdoor unit)
Indicator
Indoor unit
Operation indicator
9 time flash
Timer indicator
5 time flash
Economy indicator
Continuous flash
Error code
E: 95
outdoor unit
"Error code table (Outdoor unit)"
Detective actuator Outdoor unit
Inverter PCB
1. →hen running the compressor, if the detected rotor
location is out of phase with actual rotor location
more than 90°, the compressor stops.
2. After the compressor restarts, if the same operation
is repeated within 40 seconds, the compressor
stops again.
3. If 1. and 2. repeats 5 times, the compressor stops
permanently.
Main PCB
Compressor
Forecast of cause
Defective connection of electric components
Inverter PCB failure
Main PCB failure
Compressor failure
Check point 1. Check noise from compressor
Turn on power and check operation noise.
If an abnormal noise show, replace compres-
sor.
Check point 2. Check connection of around the compressor components
For compressor terminal, main PCB
•
Check if connector is removed.
•
Check erroneous connection.
•
Check if cable is open. (Refer to inverter compressor in
80.)
Upon correcting the removed connector or mis-wiring, reset the power.
Check point 3. Replace inverter PCB
If Check point 1, 2 do not improve the symptom, change inverter PCB.
Check point 4. Replace main PCB
If Check point 1 to 3 do not improve the symptom, change main PCB.
Check point 5. Replace compressor
If Check point 4 do not improve the symptom, change compressor.
End
2-27. E: 95.↓. Compressor motor control error (Outdoor unit)
- (03-42) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Содержание AOUH18LMAS1
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 11 01 SR_CH01_AS052EF_01 ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 11 17 SR_CH02_AS052EF_04 ...
Страница 39: ...3 TROUBLESHOOTING 2021 11 17 SR_CH03_AS052EF_01 ...
Страница 42: ......
Страница 135: ...4 CONTROL AND FUNCTIONS 2021 11 17 SR_CH04_AS052EF_01 ...
Страница 138: ......
Страница 173: ...5 FILED WORKING 2021 11 17 SR_CH05_AS052EF_01 ...