Model: AOYG24KBTB
Fan speed is defined by outdoor temperature and compressor frequency.
•
Outside air temperature zone selection
21
°C
Outside air
temperature rises
Z zone
Y zone
F zone
G zone
Outside air
temperature drops
12
°C
2
°C
-8
°C
19
°C
10
°C
0
°C
-10
°C
H zone
Unit: rpm
Fan step
Cooling
Heating
Dry
Cooling or dry at low outdoor temp.
Y zone
Y zone
Z zone
F zone
G zone
H zone
S-HIGH2
—
1,100
—
—
—
—
—
S-HIGH1
1,000
1,100
—
—
—
—
—
HIGH
1,000
1,100
—
—
—
—
—
10
—
1,100
—
—
—
—
—
9
940
940
940
770
320
320
270
8
940
940
940
630
320
320
270
7
770
700
770
470
270
270
190
6
630
550
630
270
220
220
190
5
470
470
470
270
220
220
190
4
470
440
470
270
220
220
190
3
320
440
320
270
220
220
190
2
320
440
320
270
220
220
190
1
320
440
320
270
220
220
190
NOTE:
After defrost control on the heating mode, the fan speed is kept higher regardless of the
compressor frequency.
Fan speed after defrost control: 1,100 rpm
3-2. Outdoor fan control
- (04-20) -
3. Fan control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание ABYG18KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB004EF_03 ...
Страница 24: ...2 2 Outdoor unit 01 18 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 25: ...2 TECHNICAL DATA AND PARTS LIST 2020 12 09 SR_CH02_AB004EF_05 ...
Страница 71: ...3 TROUBLESHOOTING 2020 07 01 SR_CH03_AB004EF_01 ...
Страница 74: ......
Страница 138: ...5 2 Outdoor unit 03 64 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 139: ...4 CONTROL AND FUNCTIONS 2020 07 01 SR_CH04_AB004EF_01 ...
Страница 141: ...8 8 High temperature and high pressure release control 04 42 CONTENTS continued ...
Страница 142: ......
Страница 187: ...5 FILED WORKING 2020 07 01 SR_CH05_AB004EF_01 ...