1-4. Compressor frequency at normal start-up
¢
Model: AOYG18KBTB
Compressor frequency soon after starting is controlled as below.
Frequency I
Frequency II
Frequency III
Frequency IV
Frequency V
Time 1
Time 2
Time 3
Time 4
Time 5
Frequency (rps)
I
II
III
IV
V
40
56
77
90
99
Time (sec)
1
2
3
4
5
60
240
280
360
400
¢
Models: AOYG22KBTB and AOYG24KBTB
Compressor frequency soon after starting is controlled as below.
Frequency I
Frequency II
Frequency III
Frequency IV
Frequency V
Frequency VI
Time 1
Time 2
Time 3
Time 4
Time 5
Time 6
Frequency
(rps)
I
II
III
IV
V
VI
35
52
64
71
89
97
Time (sec)
1
2
3
4
5
6
60
140
170
200
350
410
1-4. Compressor frequency at normal start-up
- (04-6) -
1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание ABYG18KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB004EF_03 ...
Страница 24: ...2 2 Outdoor unit 01 18 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 25: ...2 TECHNICAL DATA AND PARTS LIST 2020 12 09 SR_CH02_AB004EF_05 ...
Страница 71: ...3 TROUBLESHOOTING 2020 07 01 SR_CH03_AB004EF_01 ...
Страница 74: ......
Страница 138: ...5 2 Outdoor unit 03 64 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 139: ...4 CONTROL AND FUNCTIONS 2020 07 01 SR_CH04_AB004EF_01 ...
Страница 141: ...8 8 High temperature and high pressure release control 04 42 CONTENTS continued ...
Страница 142: ......
Страница 187: ...5 FILED WORKING 2020 07 01 SR_CH05_AB004EF_01 ...