Type
Ceiling
Inverter heat pump
Model name
ABYG36KRTA
ABYG45KRTA
Power supply
230 V ~ 50 Hz
Power supply intake
Outdoor unit
Available voltage range
198—264 V
Capacity
Cooling
Rated
kW
9.5
12.1
Btu/h
32,400
41,300
Min.—Max.
kW
2.8—11.2
4.0—13.5
Btu/h
9,600—38,200
13,600—46,000
Heating
Rated
kW
10.8
13.5
Btu/h
36,900
46,000
Min.—Max.
kW
2.7—12.7
4.2—16.2
Btu/h
9,200—43,300
14,300—55,300
Input power
Cooling
Rated
kW
2.96
4.22
Max.
4.52
4.79
Heating
Rated
2.88
3.84
Max.
4.31
4.81
Current
Cooling
Rated
A
13.1
18.6
Heating
12.7
16.9
EER
Cooling
kW/kW
3.21
2.87
COP
Heating
3.75
3.52
Power factor
Cooling
%
98.9
99.0
Heating
98.8
98.9
Moisture removal
L/h (pints/h)
2.6 (4.6)
4.5 (7.9)
Maximum operating current *
1
Cooling
A
22.6
28.5
Heating
22.6
28.5
Fan
Airflow rate
Cooling
HIGH
m
3
/h
1,850
1,900
MED
1,470
1,510
LOW
1,300
1,380
QUIET
1,050
1,130
Heating
HIGH
1,800
1,850
MED
1,470
1,510
LOW
1,300
1,380
QUIET
1,050
1,130
Type × Q'ty
Sirocco × 4
Motor output
W
110
Sound pressure level *
2
Cooling
HIGH
dB (A)
44
45
MED
40
41
LOW
37
39
QUIET
32
34
Heating
HIGH
44
45
MED
40
41
LOW
37
39
QUIET
32
34
Heat exchanger type
Dimensions (H × W × D)
mm
294 × 1,335 × 39.9
Fin pitch
mm
1.30
Rows × Stages
3 × 14
Pipe type
Copper
Fin type
Aluminum
Enclosure
Material
Steel sheet
Color
White
Approximate color of Munsell N9.25/
Dimensions
(H × W × D)
Net
mm
235 × 1,700 × 705
Gross
330 × 1,785 × 825
Weight
Net
kg
38
Gross
48
Connection pipe
Size
Liquid
mm (in)
Ø9.52 (Ø3/8)
Gas
Ø15.88 (Ø5/8)
Method
Flare
Drain hose
Material
PVC
Tip diameter
mm
Ø25 (I.D.), Ø32 (O.D.)
Operation range
Cooling
°C
18 to 32
%RH
80 or less
Heating
°C
16 to 30
Remote controller (Option)
Wired remote controller, Wireless remote controller, Mobile app*3 (FGLair
™
)
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Maximum current is maximum value when operated within the operation range.
• *2: Sound pressure level:
–
Measured values in manufacturer’s anechoic chamber.
–
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• *3: Available on Google Play
™
store or on App Store
®
. Optional WLAN adapter is also required. For details, refer to the setting manual.
• This data is based on EN 14511 standard.
1-1. Indoor unit
- (01-5) -
1. Specifications
GENERAL
INFORMATION
GENERAL
INFORMATION
Содержание ABYG18KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB004EF_03 ...
Страница 24: ...2 2 Outdoor unit 01 18 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 25: ...2 TECHNICAL DATA AND PARTS LIST 2020 12 09 SR_CH02_AB004EF_05 ...
Страница 71: ...3 TROUBLESHOOTING 2020 07 01 SR_CH03_AB004EF_01 ...
Страница 74: ......
Страница 138: ...5 2 Outdoor unit 03 64 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...