2-22. E: 73. Heat exchanger (Middle/Outlet) temperature
thermistor error (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: 73
Detective actuator
Heat exchanger liquid temperature
thermistor
•
Heat exchanger liquid temperature thermistor short
or open detected
•
Heat exchanger middle temperature thermistor
short or open detected
Heat exchanger middle
temperature thermistor
Forecast of cause
Connector failure
Thermistor failure
Main PCB failure
Check Point 1 : Check the connector connection and cable open
•
Connector connection state check
•
Cable open check
↓
Check Point 2 : Check the thermistor
•
For the outdoor unit heat exchanger thermistor resistance value, refer to
•
If thermistor is either open or shorted, replace it and reset the power.
↓
Check point 3. Check voltage of main PCB
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor
(DC 5.0 V).
NOTE:
For details of thermistor connector, refer to
TECHNICAL DATA AND PARTS LIST on page 02-33.
If the voltage does not appear, replace main PCB.
↓
End
2-22. E: 73. Heat exchanger (Middle/Outlet) temperature thermistor error (Outdoor
unit)
- (03-26) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание ABYG18KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB004EF_03 ...
Страница 24: ...2 2 Outdoor unit 01 18 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 25: ...2 TECHNICAL DATA AND PARTS LIST 2020 12 09 SR_CH02_AB004EF_05 ...
Страница 71: ...3 TROUBLESHOOTING 2020 07 01 SR_CH03_AB004EF_01 ...
Страница 74: ......
Страница 138: ...5 2 Outdoor unit 03 64 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 139: ...4 CONTROL AND FUNCTIONS 2020 07 01 SR_CH04_AB004EF_01 ...
Страница 141: ...8 8 High temperature and high pressure release control 04 42 CONTENTS continued ...
Страница 142: ......
Страница 187: ...5 FILED WORKING 2020 07 01 SR_CH05_AB004EF_01 ...