2-5. E: 22. Indoor unit capacity error (Indoor unit)
Detective actuator
Indoor unit main PCB
When the total capacity of the indoor units does not
match outdoor unit capacity while 3 minutes after power
on.
Forecast of cause
Indoor unit selection is incorrect.
Main PCB failure
Check point 1. Check the total capacity of indoor units
Check the total capacity of the indoor units.
→ If abnormal condition is found, correct it referring to the installation manual or DESIGN & TECH-
NICAL MANUAL.
↓
Check point 2. Replace main PCB
If check point 1 does not improve the symptom, change main PCB.
↓
End
2-5. E: 22. Indoor unit capacity error (Indoor unit)
- (03-9) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание ABYG18KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB004EF_03 ...
Страница 24: ...2 2 Outdoor unit 01 18 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 25: ...2 TECHNICAL DATA AND PARTS LIST 2020 12 09 SR_CH02_AB004EF_05 ...
Страница 71: ...3 TROUBLESHOOTING 2020 07 01 SR_CH03_AB004EF_01 ...
Страница 74: ......
Страница 138: ...5 2 Outdoor unit 03 64 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 139: ...4 CONTROL AND FUNCTIONS 2020 07 01 SR_CH04_AB004EF_01 ...
Страница 141: ...8 8 High temperature and high pressure release control 04 42 CONTENTS continued ...
Страница 142: ......
Страница 187: ...5 FILED WORKING 2020 07 01 SR_CH05_AB004EF_01 ...