7-5. Fresh air control
The fan motor for Fresh Air is operated in synchronization with the indoor fan operation as below.
Operation
Stop
Operation
Stop
Fan motor
(Indoor unit)
Fan motor
(for Fresh Air)
7-6. Compressor preheating
By preheating the compressor, warm airflow is quickly discharged when the operation is started.
•
Models: AOYG18KBTB, AOYG22KBTB, and AOYG24KBTB
–
Triggering condition
• 30 minutes after compressor stopped.
• Outdoor unit heat exchanger temperature (Tn)
-2°C
Off
On
Tn
Tn
-4°C
When the jumper wire (JM2) is disconnected:
5°C
Off
On
Tn
Tn
7°C
•
Models: AOYG30KBTB, AOYG36KBTB, and AOYG45KBTB
–
Triggering condition 1
• Outdoor temperature ≤ 20°C
When outdoor temperature reaches 26°C, compressor preheating stops.
• 30 minutes after compressor stopped
–
Triggering condition 2
0°C
Off
On
Tn
Tn
2°C
Tn: Outdoor unit heat exchanger temp.
7-5. Fresh air control
- (04-32) -
7. Various control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание ABYG18KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB004EF_03 ...
Страница 24: ...2 2 Outdoor unit 01 18 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 25: ...2 TECHNICAL DATA AND PARTS LIST 2020 12 09 SR_CH02_AB004EF_05 ...
Страница 71: ...3 TROUBLESHOOTING 2020 07 01 SR_CH03_AB004EF_01 ...
Страница 74: ......
Страница 138: ...5 2 Outdoor unit 03 64 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 139: ...4 CONTROL AND FUNCTIONS 2020 07 01 SR_CH04_AB004EF_01 ...
Страница 141: ...8 8 High temperature and high pressure release control 04 42 CONTENTS continued ...
Страница 142: ......
Страница 187: ...5 FILED WORKING 2020 07 01 SR_CH05_AB004EF_01 ...