Type
Ceiling
Inverter heat pump
Model name
ABYG24KRTA
ABYG30KRTA
Power supply
230 V ~ 50 Hz
Power supply intake
Outdoor unit
Available voltage range
198—264 V
Capacity
Cooling
Rated
kW
6.8
8.5
Btu/h
23,200
29,000
Min.—Max.
kW
0.9—8.0
2.8—10.0
Btu/h
3,100—27,300
9,600—34,100
Heating
Rated
kW
7.5
10.0
Btu/h
25,600
34,100
Min.—Max.
kW
0.9—9.1
2.7—11.2
Btu/h
3,100—31,000
9,200—38,200
Input power
Cooling
Rated
kW
2.14
2.65
Max.
2.92
4.14
Heating
Rated
1.97
2.77
Max.
2.59
4.38
Current
Cooling
Rated
A
9.5
11.7
Heating
8.7
12.2
EER
Cooling
kW/kW
3.18
3.21
COP
Heating
3.81
3.61
Power factor
Cooling
%
98.3
98.5
Heating
98.4
98.8
Moisture removal
L/h (pints/h)
2.2 (3.9)
3.0 (5.3)
Maximum operating current *
1
Cooling
A
13.6
22.6
Heating
13.6
22.6
Fan
Airflow rate
Cooling
HIGH
m
3
/h
1,230
1,400
MED
990
1,120
LOW
860
980
QUIET
700
800
Heating
HIGH
1,230
1,400
MED
990
1,120
LOW
860
980
QUIET
700
800
Type × Q'ty
Sirocco × 3
Motor output
W
80
Sound pressure level *
2
Cooling
HIGH
dB (A)
41
45
MED
36
40
LOW
32
35
QUIET
29
32
Heating
HIGH
41
45
MED
36
40
LOW
32
35
QUIET
29
32
Heat exchanger type
Dimensions (H × W × D)
mm
294 × 1,025 × 39.9
Fin pitch
mm
1.30
Rows × Stages
3 × 14
Pipe type
Copper
Fin type
Aluminum
Enclosure
Material
Steel sheet
Color
White
Approximate color of Munsell N9.25/
Dimensions
(H × W × D)
Net
mm
235 × 1,390 × 705
Gross
330 × 1,475 × 825
Weight
Net
kg
31
Gross
41
Connection pipe
Size
Liquid
mm (in)
Ø6.35 (Ø1/4)
Ø9.52 (Ø3/8)
Gas
Ø12.70 (Ø1/2)
Ø15.88 (Ø5/8)
Method
Flare
Drain hose
Material
PVC
Tip diameter
mm
Ø25 (I.D.), Ø32 (O.D.)
Operation range
Cooling
°C
18 to 32
%RH
80 or less
Heating
°C
16 to 30
Remote controller (Option)
Wired remote controller, Wireless remote controller, Mobile app*3 (FGLair
™
)
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Maximum current is maximum value when operated within the operation range.
• *2: Sound pressure level:
–
Measured values in manufacturer’s anechoic chamber.
–
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• *3: Available on Google Play
™
store or on App Store
®
. Optional WLAN adapter is also required. For details, refer to the setting manual.
• This data is based on EN 14511 standard.
1-1. Indoor unit
- (01-3) -
1. Specifications
GENERAL
INFORMATION
GENERAL
INFORMATION
Содержание ABYG18KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB004EF_03 ...
Страница 24: ...2 2 Outdoor unit 01 18 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 25: ...2 TECHNICAL DATA AND PARTS LIST 2020 12 09 SR_CH02_AB004EF_05 ...
Страница 71: ...3 TROUBLESHOOTING 2020 07 01 SR_CH03_AB004EF_01 ...
Страница 74: ......
Страница 138: ...5 2 Outdoor unit 03 64 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 139: ...4 CONTROL AND FUNCTIONS 2020 07 01 SR_CH04_AB004EF_01 ...
Страница 141: ...8 8 High temperature and high pressure release control 04 42 CONTENTS continued ...
Страница 142: ......
Страница 187: ...5 FILED WORKING 2020 07 01 SR_CH05_AB004EF_01 ...