3-4. No cooling/No heating
Forecast of cause
Indoor unit error
Outdoor unit error
Effect by surrounding environment
Connection pipe/Connection wire failure
Refrigeration cycle failure
Check point 1. Check Indoor unit
•
Does Indoor unit fan run in the HIGH mode?
•
Is air filter dirty?
•
Is heat exchanger clogged?
•
Check if energy save function is operated.
↓
Check point 2. Check outdoor unit operation
•
Check if outdoor unit is operating.
•
Check any objects that obstruct the air flow route.
•
Check if heat exchanger is clogged.
•
Is the valve open?
↓
Check point 3. Check site condition
•
Is capacity of Indoor unit fitted to the room size?
•
Any windows open or direct sunlight?
↓
Check point 4. Check Indoor/ Outdoor installation condition
•
Check connection pipe (specified pipe length and pipe diameter?)
•
Check any loose or removed communication line.
→ If there is an abnormal condition, correct it by referring to the installation manual or the “DESIGN
& TECHNICAL MANUAL”.
↓
Check point 5. Check Refrigeration cycle
•
Check if strainer is clogged (Refer to the figure below).
•
Measure gas pressure, and if there is a leakage, correct it.
•
Check the electronic expansion valve.
Refer to outdoor unit Electronic Expansion Valve (EEV) in
•
Check compressor.
Refer to compressor in
Refer to inverter compressor in
NOTE:
When recharging the refrigerant, make sure to perform vacuuming,
and recharge the specified amount.
MPa
MPa
↓
End
3-4. No cooling/No heating
- (03-42) -
3. Troubleshooting without error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание ABYG18KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB004EF_03 ...
Страница 24: ...2 2 Outdoor unit 01 18 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 25: ...2 TECHNICAL DATA AND PARTS LIST 2020 12 09 SR_CH02_AB004EF_05 ...
Страница 71: ...3 TROUBLESHOOTING 2020 07 01 SR_CH03_AB004EF_01 ...
Страница 74: ......
Страница 138: ...5 2 Outdoor unit 03 64 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 139: ...4 CONTROL AND FUNCTIONS 2020 07 01 SR_CH04_AB004EF_01 ...
Страница 141: ...8 8 High temperature and high pressure release control 04 42 CONTENTS continued ...
Страница 142: ......
Страница 187: ...5 FILED WORKING 2020 07 01 SR_CH05_AB004EF_01 ...