Peak cut mode
1.
Press the MODE switch button (S134) for 3 seconds or more to switch to “Local setting mode”.
2.
After confirming the LED lamp of POWER/MODE blinks 9 times, press the ENTER switch but-
ton (S132).
POWER
MODE
ERROR
(L1)
(L2)
(L3)
(L4)
(L5)
(L6)
PUMP
DOWN
LOW NOISE
PEAK CUT
Blinks
(9 times
)
Sign “
”: Lights off
3.
Press the SELECT switch button (S133), and adjust the LED lamp as shown below. Then the
LED lamp indicates the current setting.
(L2)
(L3)
LOW NOISE
Blink
PEAK CUT
MOD
E
4.
Press the ENTER switch button (S132).
(L2)
(L3)
LOW NOISE
PEAK CUT
MODE
Sign “ ”: Lights on
5.
Press the SELECT switch button (S133), and adjust the LED lamps as shown below.
0 % of rated input ratio
50 % of rated input ratio
75 % of rated input ratio
100 % of rated input ratio
Blink
Blink
Blink
Blink
Blink
PEAK CUT
(L4)
(L5)
(L6)
6.
Press the ENTER switch button (S132) and fix it.
0 % of rated input ratio
50 % of rated input ratio
75 % of rated input ratio
100 % of rated input ratio
PEAK CUT
(L4)
(L5)
(L6)
7.
To return to “Operating status display (Normal operation)”, press the EXIT switch button
(S131).
NOTE:
When pressed number is lost during setting, you must redo the setting procedure. Return to
“Operation status display (Normal operation)” by pressing the EXIT switch button once, and
restart from the beginning of the setting procedure.
1-2. Function settings on outdoor unit
- (05-8) -
1. Function settings (For indoor unit)
FIELD
WORKING
FIELD
WORKING
Содержание ABYG18KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB004EF_03 ...
Страница 24: ...2 2 Outdoor unit 01 18 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 25: ...2 TECHNICAL DATA AND PARTS LIST 2020 12 09 SR_CH02_AB004EF_05 ...
Страница 71: ...3 TROUBLESHOOTING 2020 07 01 SR_CH03_AB004EF_01 ...
Страница 74: ......
Страница 138: ...5 2 Outdoor unit 03 64 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 139: ...4 CONTROL AND FUNCTIONS 2020 07 01 SR_CH04_AB004EF_01 ...
Страница 141: ...8 8 High temperature and high pressure release control 04 42 CONTENTS continued ...
Страница 142: ......
Страница 187: ...5 FILED WORKING 2020 07 01 SR_CH05_AB004EF_01 ...