4-3. Outdoor unit Electronic Expansion Valve (EEV)
¢
Models: AOYG18KBTB, AOYG22KBTB, and AOYG24KBTB
Check point 1. Check connections
Check connection of connector. (Loose connector or open cable)
NOTE:
For details of wiring diagram, refer to
Check point 2. Check coil of EEV
Remove connector, check each winding resistance of coil.
Read wire
Resistance value
White - Red
46 Ω ± 3.7 Ω
at 20°C
Yellow - Red
Orange - Red
Blue - Red
→ If Resistance value is abnormal, replace EEV.
Check point 3. Check voltage from main PCB
Remove connector and check voltage (DC 12 V)
→ If it does not appear, replace main PCB.
Check point 4. Check noise at start up
Turn on the power and check the operation noise.
→ If an abnormal noise does not show, replace main PCB.
Check point 5. Check opening and closing operation of valve
When valve is closed, it has a temp. difference
between inlet and outlet
Pipe (In)
Pipe (Out)
Hi TEMP.
Normal TEMP.
CLOSE
Example : Hot Gas
If it is open, it has no temp. difference between
inlet and outlet
Pipe (In)
Hi TEMP.
OPEN
Example : Hot Gas
Pipe (Out)
Hi TEMP.
4-3. Outdoor unit Electronic Expansion Valve (EEV)
- (03-51) -
4. Service parts information
TROUBLESHOOTING
TROUBLESHOOTING
Содержание ABYG18KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB004EF_03 ...
Страница 24: ...2 2 Outdoor unit 01 18 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 25: ...2 TECHNICAL DATA AND PARTS LIST 2020 12 09 SR_CH02_AB004EF_05 ...
Страница 71: ...3 TROUBLESHOOTING 2020 07 01 SR_CH03_AB004EF_01 ...
Страница 74: ......
Страница 138: ...5 2 Outdoor unit 03 64 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 139: ...4 CONTROL AND FUNCTIONS 2020 07 01 SR_CH04_AB004EF_01 ...
Страница 141: ...8 8 High temperature and high pressure release control 04 42 CONTENTS continued ...
Страница 142: ......
Страница 187: ...5 FILED WORKING 2020 07 01 SR_CH05_AB004EF_01 ...