Set - Cleaning
System menu
System
Setting
Cleaning
Clean after how many hours heating?
If the boiler has passed the set time in “
Heating
” status,
the boiler shuts down for a cleaning cycle.
Tip grate 1 how often during cleaning?
Defines the number of times the first combustion grate is
tipped during “
Tip grate
” status.
Tip grate 2 how often during cleaning?
Prerequisite: Boiler with separately driven second
combustion grate
Defines the number of times the second combustion grate
is tipped during “
Cleaning
” status.
Tip grate 1 after how many times cleaning
Indicates the number of cleanings after which the grate on
the feed-in side is tilted.
Tip grate 1 after how many hours heating
Indicates after how many hours of heating the grate on the
feed-in side is tilted.
Permitted start processes with blocked ash screw
Defines the number of boiler start processes that can be
carried while the ash screw is blocked. Once the specified
number has been reached, no further start process is
permitted
The cleaning may start from
Time from which cleaning is enabled. A time limit for the
heat exchanger is not recommended.
The cleaning may run until
Time from which cleaning is blocked. A time limit for the
heat exchanger function is not recommended.
Runtime of the cleaning per heating hour
Specifies how long the cleaning per operating hour of the
boiler should be in the heating status. If the boiler is
switched off after 5 hours of heating operation, cleaning
takes five times as long as the time set here.
Minimum duration shutdown
Minimum duration of “
Awaiting shutdown
” status, in
which the remaining fuel is burned on the combustion
grate.
Cleaning after standby
▪ YES: When the boiler switches off, the combustion
chamber grate is only tipped and cleaned after the next
start command. The remaining bed of embers cools
down and when fully cooled falls into the ash screw.
▪ NO: In “
Cleaning
” operating status, the combustion
grate is tipped and cleaned.
Parameters overview
4
System
Service manual Lambdatronic H 3200 for wood chip boiler | B1480721_en
109